| 2021-11-17 13:11:07 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG. |
| | SERVICES DEPT., 561-494-1098 [email protected] : |
| | |
| | GENERAL: |
| | O PLEASE RESPOND TO ALL COMMENTS IN WRITING, AND |
| | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER |
| | (Z-XXXXXXXX). |
| | O THE CITY OF WEST PALM BEACH HAS A NUMBER OF |
| | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY |
| | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND |
| | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE |
| | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK |
| | BELOW: |
| | A. HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WP |
| | B_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FUL |
| | L-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97 |
| | B1960045731D3658206F27451722716EF |
| | B. THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE |
| | FOUND HERE: |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | C. ALSO SEE: CODE OF ORDINANCES, CITY OF WEST PALM |
| | BEACH, FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, |
| | ADOPTED SEPT. 22, 2008. (SUPPLEMENT NO. 18) |
| | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, |
| | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER |
| | SERVICE FACILITIES OF THE CITY. |
| | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE |
| | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY |
| | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, |
| | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. |
| | O AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| | MORE INFORMATION, REFER TO THE LINK BELOW: |
| | A. HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PU |
| | BLICATIONS/BACKFLOW-CROSS-CONNECTION- CONTROL-MANUAL |
| | O PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY |
| | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC |
| | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF |
| | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| | [email protected] OR 561-494-1079 FOR FURTHER |
| | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION |
| | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD |
| | SURVEY, POT-HOLING, SOFT DIGS ETC. |
| | |
| | BACKFLOW ASSEMBLY AND METERS: |
| | |
| | O SHOW AND LABEL ANY EXISTING OR PROPOSED WATER |
| | SERVICES AND WATER METERS FOR THE PARKING LOTS, ALONG |
| | WITH WHAT IS HAPPENING TO THEM. |
| | O SHOW EXISTING AND PROPOSED DEDICATED UTILITY |
| | EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO |
| | PROPOSED UTILITY WATER METERS. VERIFY THAT THERE ARE NO |
| | STRUCTURES WITHIN EASEMENT. |
| | O PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED LOCATION |
| | OF WATER METER AND BACKFLOW |
| | PREVENTION. |
| | O BACKFLOWS SHALL BE INSTALLED ON PRIVATE PROPERTY |
| | OUTSIDE OF EASEMENTS AND RIGHTS OF WAY. DOMESTIC WATER |
| | METERS SHALL BE INSTALLED IMMEDIATELY ADJACENT TO |
| | PROPERTY LINE. 3 INCH AND LARGER WATER METERS SHALL BE |
| | INSTALLED ABOVE-GROUND ONLY. |
| | O CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA (MAKE |
| | NOTE USC APPROVED) AND FIRE BACKFLOW PREVENTER AS DCDA. |
| | |
| | WATER/WASTEWATER PLAN: |
| | O PROVIDE VERTICAL DATUM AND DATUM CONVERSION |
| | INFORMATION (NAVD 1988 AND NGVD 1929). |
| | O SHOW PROJECT ADDRESS ON ALL PLAN SHEETS. |
| | O PROVIDE LEGEND ON ALL PLAN SHEETS TO INCLUDE |
| | STREETLIGHT, SIGN POSTS, TRANSFORMER BOXES ETC. |
| | O PLANS SHALL SHOW EXISTING AND PROPOSED LOCATIONS AND |
| | DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND |
| | SEWER LINES AND CLEANOUTS, INCLUDING STUBS TO EACH |
| | PROPERTY LINE FOR WATER AND SANITARY SEWERS, THE MAKE |
| | AND MODEL OF ALL VALVES, POTABLE AND IRRIGATION METERS, |
| | BACKFLOWS, FIRE HYDRANTS AND FDCS, AND OTHER DEVICES TO |
| | BE INSTALLED ON THE SYSTEM, CATCH BASINS, CULVERTS, |
| | DITCHES INCLUDING GRADES, PIPES SIZES, MATERIALS, |
| | ELEVATIONS, ASSUMPTIONS, CALCULATIONS, INVERT |
| | ELEVATIONS FOR ALL INLETS AND MANHOLES AND PROFILES OF |
| | SANITARY SEWER LINES. |
| | O GATE VALVE BOXES SHALL NOT BE INSTALLED IN CURB OR |
| | SIDEWALK. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. |
| | O DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN |
| | VIEW FOR ALL SANITARY AND STORM SEWERS. |
| | O SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT |
| | MATERIAL. |
| | O PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED |
| | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, |
| | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION |
| | FACILITIES LOCATED ON THE RIGHT-OF-WAY. |
| | O PROVIDE PROFILE AND CLEARANCES BETWEEN WATER, SEWER |
| | AND STORM LINES PER CITY OF WEST PALM BEACH STANDARD |
| | DETAIL GN-2 SERIES, AT ALL UTILITY CROSSINGS. |
| | O SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE DIRECTLY |
| | TO ENGINEERING (SHEET 33 OF CITY OF WPB DEVELOPMENT |
| | APPLICATION). PROVIDE CALCULATIONS ON PLANS OF EXISTING |
| | AND PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, |
| | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS |
| | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 |
| | FOR WATER. |
| | O PROVIDE FIRE FLOW TEST DATA. |
| | O PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND |
| | STORMWATER INFRASTRUCTURE ALONG ENTIRE PROJECT |
| | FRONTAGE. |
| | O CUT AND CAP UTILITIES NOT IN USE AND REMOVE ANY |
| | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY |
| | ROW. |
| | O WHEN PROPOSED, WATER MAINS IN CITY RIGHT OF WAY SHALL |
| | BE MADE OF DUCTILE IRON PIPE (NOT PVC) AND SPECIFY |
| | PROPOSED LENGTH IN FEET. |
| | O CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY |
| | SEWER ARE REQUIRED. |
| | O PROVIDE CLEANOUTS FOR PROPOSED SANITARY LINE ONSITE |
| | JUST INSIDE PROPERTY LINE, AT JOINTS AND EVERY 75 FEET. |
| | O ADD NOTE TO PLANS SPECIFYING CITY?S DOWNSTREAM LIFT |
| | STATION NUMBER. |
| | O PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR |
| | PROPOSED SANITARY LATERALS. |
| | O LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. |
| | O PLEASE SHOW AND LABEL EXISTING AND PROPOSED GREASE |
| | TRAPS (IF ANY). |
| | O PER CITY STANDARDS MAINTAIN MINIMUM DISTANCE BETWEEN |
| | OUTSIDE DIAMETER OF CITY PIPE AND ROOT BARRIER. |
| | |
| | FORMAL ENGINEERING REVIEW: |
| | O FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND NPDES |
| | NOI REQUIREMENTS WILL BE ENFORCED. |
| | - AN NOI IS REQUIRED FOR PROJECTS THAT: |
| | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS |
| | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF |
| | DEVELOPMENT OR SALE; |
| | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE |
| | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A |
| | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). |
| | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF |
| | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION |
| | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL |
| | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT |
| | OF THE 10-2 CERTIFICATION. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES OF |
| | WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING |
| | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT |
| | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING |
| | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED |
| | LEAD-FREE DESIGN. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES |
| | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY |
| | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT |
| | PARCELS. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES ARE |
| | BEING REPLACED IN ROW, SHOW ADJACENT PARCEL ADDRESSES. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO PROVIDE |
| | 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF |
| | PROPOSED TRENCH IN CITY MAINTAINED ROADWAY AREAS PER |
| | CITY OF WPB STANDARD DETAIL GC-8. |
| | O FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE |
| | CALCULATIONS OF PERVIOUS AND IMPERVIOUS AREAS FOR |
| | PROPOSED IMPROVED AREAS. |
| | |
| | QUESTIONS AND COORDINATION CONTACTS: |
| | O MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR WITH |
| | CITY OF WPB PUBLIC UTILITIES, REGARDING PLACEMENT OF |
| | BACKFLOW DEVICES AND WATER METERS. CONTACT HIM AT |
| | 561-494-2262 OR [email protected] |
| | O RICK ROSSANO, SR. PROJECT COORDINATOR, ENGINEERING |
| | SERVICES DEPARTMENT AT 561-494-1098 [email protected] |
| | O MIKE TECHNOW, PROJECT ENGINEER, PUBLIC UTILITIES |
| | DEPARTMENT AT 561-494-1047 OR [email protected] |
| | O TRACY WARD, SR. STORMWATER ENGINEER, ENGINEERING |
| | SERVICES DEPT. AT 561-494-1120 OR [email protected] |
| | |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR |
| | [email protected]: |
| | |
| | -THERE ARE MANY MONITORING WELLS AS SHOWN ON THE |
| | SURVEY. WILL THEY REMAIN? |
| | |
| | -FOR EASTERN BUILDING NUMBER 4 ON UTILITY PLAN: THE |
| | LEADER LINES FOR THE WATER SERVICES APPEAR TO BE |
| | POINTING WRONG; METER BOX SHOULD NOT BE IN |
| | SIDEWALK/HARDSCAPE; BACKFLOW ASSEMBLIES NOT ALLOWED IN |
| | PROPOSED LOCATION UNLESS SIDEWALK ENDS IMMEDIATELY EAST |
| | OF BACKFLOW ASSEMBLIES AND WILL NOT BE CONTINUED; |
| | UTILITY EASEMENT REQUIRED FOR WATER METER AND UPSTREAM |
| | PIPING; SEWER LATER IS CLOSE TO TREE PLANTER; DISTANCE |
| | CALLOUT NEEDED BETWEEN SEWER LATERAL AND WATER SERVICE. |
| | |
| | -UTILITY PLANS SHOW MULTIPLE BUILDINGS LABELED AS |
| | NUMBER 4. |
| | |
| | -SEWER LATERAL FOR WESTERN BUILDING NUMBER 4 HAS SEWER |
| | LATERAL RUNNING THROUGH TREE PLANTER. |
| | |
| | -ARE CROSS WALKS NEEDED AT NEW INTERSECTION OF BROADWAY |
| | AND 23RD? (EITHER EAST-WEST OR NORTH-SOUTH) |
| | |
| | -EXISTING TRAFFIC SIGN AT NORTHWEST INTERSECTION OF |
| | BROADWAY AND 23RD IS IN CLOSE PROXIMITY TO PROPOSED |
| | STORMWATER UTILITY. |
| | |
| | -PROPOSED TREE PLANTER ON 23RD STREET IS CONFLICTING |
| | WITH LARGE UTILITY POLE. |
| | |
| | -ALL OF THE SEWER MAINS IN THE AREA ARE OLDER AND MAY |
| | REQUIRE UPGRADE OR REPLACEMENT AS ADVISED BY ENGINEER |
| | OF RECORD AND/OR CITY OF WEST PALM BEACH. |
| | |
| | -SHEET C3.10, REPLACE STANDARD DETAIL WS-4 WITH WS-3. |
| | METERS 3 INCHES OR LARGER NEED TO BE ABOVE-GROUND |
| | INSTALLED. |
| | |
| | -SUBMIT SEPARATE LANDSCAPING PLAN SHOWING ALL EXISTING |
| | AND PROPOSED TREES. ON ONE OF THE PLAN SHEETS HAVE |
| | LANDSCAPING OVERLOAD ON UTILITIES SO CAN RECOGNIZE ANY |
| | CONFLICTS. |
| | |
| | -ON NORTH SIDE OF WESTERN BUILDING 4, DO PLANTERS |
| | PREVENT WALKING ALONG SIDEWALK? |
| | |
| | -SOME CANOPY OVERHANGS ON NORTHWOOD APPEAR TO EXTEND |
| | INTO ROW. PLEASE VERIFY THAT IS ACCEPTABLE. |
| | |
| | -ADD PRIVATE TO LABEL OF ANY PRIVATELY OWNED AND |
| | MAINTAINED UTILITY INFRASTRUCTURE. |
| | |
| | -DID NOT SEE ANY FDC. ARE ANY NEEDED OR REQUIRED? |
| | |
| | -UTILITY PLAN SHOWS STREET SIGN, UTILITY POLE, AND GUY |
| | WIRES IN SIDEWALK AT NORTHWEST INTERSECTION OF PINEWOOD |
| | AND 23RD. |
| | |
| | -SIDEWALK EASEMENT MAY BE REQUIRED FOR NORTHSIDE OF |
| | 23RD ST. |
| | |
| | -ADJUST LOCATION OF FIRE HYDRANT AT NORTHWOOD AND |
| | PINEWOOD INTERSECTION SUCH THAT IT DOES NOT ENCROACH IN |
| | SIDEWALK AND HAS MORE CLEARANCE DISTANCE FROM |
| | STORMWATER UTILITY. |
| | |
| | -BACKFLOW ASSEMBLIES MUST BE LOCATED ON PRIVATE |
| | PROPERTY. CANNOT BE ONLY IN RIGHT OF WAY. |
| | |
| | -ENSURE FIRELINE BACKFLOW ASSEMBLY LOCATIONS ARE NFPA |
| | COMPLIANT. |
| | |
| | -ADD PROPOSED METER SIZING. IF METERS ARE 3 INCHES OR |
| | LARGER, THE SCALE FOOTPRINT IS LIKELY MUCH SMALLER THAN |
| | WHEN BUILT OUT AND WOULD CONFLICT WITH PROPOSED |
| | LOCATIONS. |
| | |
| | -LABEL ALL EXISTING AND PROPOSED FIRE HYDRANTS. SEE AT |
| | LEAST ONE MISSING LABELING. |
| | |
| | -FIRE HYDRANT AT BROADWAY AND 24TH MAY NOT MEET |
| | STANDARD DETAIL CLEARANCE REQUIREMENTS IF A TREE IS |
| | PLANTED NEAR IT. |
| | |
| | -SHOW AND LABEL ALL EXISTING WATER SERVICE LINES, METER |
| | BOXES, METERS, SEWER LATERALS, BACKFLOW ASSEMBLIES IN |
| | THE PROJECT AREA AND LABEL WHAT IS HAPPENING TO THEM. |
| | SEE MANY NOT SHOWN AND/OR LABELED. |
| | |
| | -BUILDING 3 FIRELINE CONFLICTS WITH A MONITORING WELL. |
| | |
| | -8 INCH FIRELINE: IS MISSING POINT OF SERVICE GATE |
| | VALVE; CONFLICTING WITH SOME KIND OF UTILITY BOX; IS IN |
| | MIDDLE OF SIDEWALK; DOES NOT HAVE PIPE DISTANCE |
| | MINIMIZED BETWEEN BACKFLOW ASSEMBLY AND WATER MAIN. |
| | |
| | -UTILITY PLAN SHOWS STREET SIGN IN PROPOSED PARKING |
| | SPOT AT BUILDING 2. |
| | |
| | -PROPOSE SEWER MANHOLE NEAR BUILDING 2 IS HALF IN |
| | STREET AND SIDEWALK MAKING MAINTENANCE MORE DIFFICULT. |
| | ALSO IF PRIVATE ADD TO LABEL. |
| | |
| | -TREE OR BUSH BLOCKING DRIVEWAY OF BUILDING 2 ON |
| | UTILITY PLAN. |
| | |
| | -THERE ARE SMALL CIRCULAR OBJECTS ON UTILITY PLAN NEAR |
| | PARKING SPOTS. IF THEY ARE BOLLARDS ADD TO LEGEND OR |
| | LABEL THEM. |
| | |
| | -WATER MAIN IN PINEWOOD IS OLDER AND MAY REQUIRE |
| | UPGRADE OR REPLACEMENT AS ADVISED BY ENGINEER OF RECORD |
| | AND/OR CITY OF WEST PALM BEACH. |
| | |
| | -23RD ST IS ONE-WAY GOING WEST UNTIL PINEWOOD. MAKE |
| | SURE PLANS ACCOUNT FOR THE ONE-WAY DRIVING DIRECTION. |
| | |
| | -SHOW LOCATIONS OF PROPOSED TRANSFORMER PADS WHEREVER |
| | OVERHEAD ELECTRIC UTILITIES ARE BEING UNDERGROUNDED. |
| | |
| | -SHOW ALL EXISTING DRIVEWAY APPROACHES AND LABEL ANY |
| | THAT ARE BEING REMOVED ON THE DEMO PLANS. FOR EXAMPLE, |
| | CANNOT TELL WHAT IS HAPPENING TO THE DRIVEWAY APPROACH |
| | AT 23RD ON THE SOUTH SIDE OF 701 23RD ST. |
| | |
| | -PLEASE MAKE SURE CURB TYPES ARE LABELED ON ALL SHEETS |
| | OF THE PAVING, GRADING, AND DRAINAGE PLANS. |
| | |
| | -REMOVAL, RELOCATION, OR ALTERATION OF CITY WPB METERED |
| | WATER SERVICES AND BACKFLOW ASSEMBLIES IN PROJECT AREA |
| | WOULD REQUIRE APPROVAL FROM ASSOCIATED DEPARTMENT |
| | REPRESENTATIVES. THEY TYPICALLY REQUIRE PROJECT TO PAY |
| | ANY ASSOCIATED UTILITY BILLING CHARGES OR FEES. |
| | |
| | -ADD WATER DEMAND CALCULATIONS TO UTILITY PLAN SHEETS. |
| | |
| | -EASEMENTS MAY BE REQUIRED FOR BUILDING STRUCTURES |
| | CROSSING RIGHT OF WAY. |
| | |
| | -PROVIDE VERTICAL CLEARANCE DISTANCE FOR ANY STRUCTURES |
| | OVER STREETS, AND ENSURE LARGE UTILITY VEHICLES SUCH AS |
| | VACUUM TRUCKS WILL HAVE SUFFICIENT CLEARANCE. |
| | |
| | -ON DEMO PLAN LABEL WHAT IS HAPPENING TO THE LARGE |
| | UTILITY POLES AT THE NORTHWEST CORNER OF BUILDING 1 |
| | LOADING DRIVEWAY. |
| | |
| | -SOME OF THE VEHICLE MOVEMENTS AND SIGNAGE ARE NOT |
| | CLEAR FROM THE PLANS. FOR EXAMPLE, HOW WILL DRIVERS |
| | HEADING EAST ON 25TH KNOW NOT TO PULL INTO LOADING BAY |
| | FOR BUILDING 1. HOW WILL TRUCKS BACK UP INTO THAT BAY |
| | WITHOUT CREATING TRAFFIC PROBLEMS? |
| | |
| | -WATER UTILITIES ON 24TH ST BETWEEN PINEWOOD AND |
| | BROADWAY SHOULD BE REMOVED OR RELOCATED. |
| | |
| | -SHOW ALL GREASE TRAPS/INTERCEPTORS. |
| | |
| | -PROPOSED CURB DESIGN ON EAST SIDE OF PINEWOOD MAKES |
| | EXCAVATION AND MAINTENANCE OF EXISTING WATER MAIN |
| | DIFFICULT. |
| | |
| | -ALLEY BETWEEN 24TH AND NORTHWOOD HAS OVERHEAD |
| | UTILITIES WITH POLES THAT LOOK TO CONFLICT WITH |
| | PROPOSED BUILDINGS. |
| | |
| | -BUILDING 6 METERED WATER SERVICE NEEDS UTILITY |
| | EASEMENT SHOWN AND LABELED. VERIFY AREA AROUND METER |
| | BOX WILL BE LANDSCAPING AND NOT HARDSCAPE. |
| | |
| | -BUILDING 5 METERED WATER SERVICE NEEDS A UTILITY |
| | EASEMENT IF ON PRIVATE PROPERTY. METER BOX SHOULD NOT |
| | BE IN HARDSCAPE. METER BOX AND BACKFLOW ASSEMBLY SHOULD |
| | NOT BE IN MIDDLE OF SIDEWALK TRAFFIC. |
| | |
| | -THERE IS A LOT OF GAS UTILITIES BUT NOT SHOWING ON |
| | UTILITY PLANS. PLEASE SHOW ALL FRANCHISE AND DRY |
| | UTILITIES. |
| | |
| | -SEWER CLEANOUT FOR BUILDING 5 IS IN FRONT OF DOOR |
| | CREATING MAINTENANCE CONFLICT. |
| | |
| | -DID NOT SEE DEDICATED FIRELINES FOR BUILDINGS ON WEST |
| | SIDE OF PINEWOOD. ARE ANY NEEDED OR REQUIRED? |
| | |
| | -SHOW PAVEMENT RESTORATION BOUNDARIES FOR ALL UTILITY |
| | WORK INCLUDING 25TH ST AND 23RD ST. MAKE SURE THE |
| | BOUNDARIES COMPLY WITH DISTANCE REQUIREMENTS ON |
| | STANDARD DETAILS. |
| | |
| | -IS THE NEW CONNECTING ROAD BETWEEN NORTHWOOD AND 23RD |
| | INTENDED FOR PUBLIC USE? ARE ANY EASEMENTS NEEDED FOR |
| | IT SINCE ON PRIVATE PROPERTY? VERIFY IT WILL BE |
| | PRIVATELY MAINTAINED. |
| | |
| | -SEWER MAINS IN ALLEYS MAY NEED RELOCATION AS ADVISED |
| | BY ENGINEER OF RECORD AND/OR CITY OF WEST PALM BEACH. |
| | |
| | -SEWER MAIN IS SHOWN ON UTILITY PLANS ON WEST SIDE OF |
| | BROADWAY IN PROPOSED SIDEWALK. LOCATION WOULD MAKE |
| | EXCAVATION AND MAINTENANCE DIFFICULT. SOME PROPOSED |
| | TREE PLANTER LOCATIONS ON TOP OF SEWER MAIN ALSO |
| | CONFLICT WITH MAINTENANCE AS WELL AS SOME CURBING AT A |
| | MANHOLE. |
| | |
| | -DOMESTIC WATER SERVICES TYPICALLY ARE NOT 3 INCH. 3 |
| | INCH METERS HAVE 4 INCH DIP SERVICE PIPE SHOWN ON |
| | STANDARD DETAILS. |
| | |
| | -ADD ELEVATION INFO TO SEWER MANHOLE LABELS. |
| | |
| | COMMENTS FROM MICHAEL TECHNOW, PROJECT ENGINEER, WPB |
| | PUBLIC UTILITIES, 561-494-1047, [email protected] : |
| | |
| | PLEASE REPLACE 24? WM ON PINEWOOD WITHIN LIMITS OF THE |
| | PROPOSED IMPROVEMENTS. |
| | - PROVIDE PROFILE FROM TAP TO POINT OF SERVICE. |
| | -REVISE UTILITY NOTES TO REFLECT ?CITY OF WEST PALM |
| | BEACH? NOT PBCWUD/COUNTY. |
| | - NO 3? SERVICES ALLOWED. USE EITHER 2? OR 4? WITH A |
| | REDUCER. |
| | -ADD NOTE TO CUT AND CAP ABANDONED SERVICES AT THE |
| | MAIN. |
| | |
| | COMMENTS FROM BURT BAIRD, CITY OF WPB UTILITIES O&M |
| | SUPERINTENDENT, 561-822-2056, [email protected] : |
| | ? PLEASE ENSURE ADDED FLOW CAN BE HANDLED AT LS# 23 |
| | ? KIMBERLY HORN MENTIONED AN ADDITIONAL FLOW OF 54000 |
| | GALLONS ? SEE EMAILED DOCUMENT |
| | ? THE COLLECTION SYSTEM AT THIS STATION EXPERIENCES |
| | HIGH AMOUNTS OF I&I. ANY PLANS ON THIS BEING ADDRESSED? |
| | ? I&I PUTS THE PUMPS AT THIS STATION ON LONG RUN TIMES |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | |
| |