2023-02-17 17:15:16THESE COMMENTS ARE FROM THE REVIEW OF THE 2/10/2023
 SUBMITTAL:
  
 1. SIDEWALK RAMP BETWEEN STREET SIDEWALK AND THE
 PARKING LOT WILL NEED HANDRAILS PER THE FBC
 ACCESSIBILITY CHAPTER (SLOPE IS IN EXCESS OF 5% AND
 MORE THAN 6 INCHES HIGH). THE HANDRAILS CANNOT EXTEND
 INTO THE RIGHT OF WAY. A LEVEL LANDING MAY BE REQUIRED
 AT THE TOP OF THE RAMP. THE SLOPE MAY BE RESTRICTED TO
 LESS THAN 5% IF A PORTION OF THE SIDEWALK RUNS N-S
 ALONG THE BUILDING ANF THEN TURNS TO THE WEST TO THE
 RIGHT OF WAY.
  
 2. 5-YEAR RUNOFF DEPTH WILL BE 4.22 INCHES (=0.35 FT)
 (SCS FORMULA. P = 6 INCHES; AVG S = 1.88 INCHES). 5-YR
 RUNOFF VOLUME WILL BE 2247 C.F. (0.35 FT X 6420 S.F.).
  
 3. IF THE PAVEMENT CUT FOR THE SEWER LATERAL EXTENDS
 PAST THE ROAD CENTERLINE, THEN THE MILL AND RESUFACE
 LIMITS WILL NEED TO EXTEND TO THE EDGE OF THE
 SOUTHBOUND TRAVEL LANE (EDGE OF PARKING SPACE) AND 50
 FEET NORTH AND SOUTH OF THE SEWER LATERAL.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT