| 2022-02-01 10:04:43 | COMMENTS FOR THE REFERENCED PROJECT: | | | SHEET C-1: | | | -ADD A NOTE OR CALL OUT FOR EXISTING SERVICE TO BE CUT | | | AND CAPPED AT THE MAIN IF BEING ABANDONED/RELOCATED. | | | SHEET C-2 | | | -SHOW PROFILE VIEW OF TIE-INS FROM TAP TO POINT OF | | | SERVICE (PROPERTY LINE) SHOWING VERTICAL CLEARANCES AND | | | ANY CONFLICTS. | | | -CALL OUT CLARE AVE ROW LINES. | | | | | | CONTACT MIKE TECHNOW [email protected] OR 561-494-1047 | | | WITH ANY QUESTIONS. |
| |