2022-02-01 10:04:43COMMENTS FOR THE REFERENCED PROJECT:
 SHEET C-1:
 -ADD A NOTE OR CALL OUT FOR EXISTING SERVICE TO BE CUT
 AND CAPPED AT THE MAIN IF BEING ABANDONED/RELOCATED.
 SHEET C-2
 -SHOW PROFILE VIEW OF TIE-INS FROM TAP TO POINT OF
 SERVICE (PROPERTY LINE) SHOWING VERTICAL CLEARANCES AND
 ANY CONFLICTS.
 -CALL OUT CLARE AVE ROW LINES.
  
 CONTACT MIKE TECHNOW [email protected] OR 561-494-1047
 WITH ANY QUESTIONS.