Date Text
2021-08-11 14:05:19RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPT., 561-494-1098 [email protected] :
  
 NO COMMENTS.
  
 COMMENTS PER MARK HURLEY, CITY OF WPB PUB. UTIL. FIELD
 CUSTOMER SVC. SUPV., [email protected]. 561-822-2262:
  
 -ENGINEERING PLAN IS DATED FROM 2018 AND INCLUDES WATER
 SERVICE STANDARD DETAILS THAT ARE OLD REVISION OR NO
 LONGER STANDARD. PLEASE UPDATE PLANS TO REFLECT CURRENT
 WATER SERVICE STANDARD DETAILS.
 -PLEASE ENSURE ALL WATER MAINS WILL HAVE UTILITY
 EASEMENTS. FOR INSTANCE, THE 8 INCH DIP WATER MAIN
 ACROSS BANEBERRY LANE FROM LOT 19 DOES NOT SEEM TO HAVE
 ONE.
 -NEW HOUSES IN OTHER SECTIONS OF BANYAN CAY ARE GETTING
 ELECTRIC TRANSFORMERS INSTALLED ON PADS IN FRONT OF
 HOUSES IN UTILITY EASEMENT, BUT DO NOT SEEM ANY ON THE
 ENGINEERING PLAN. PLEASE ADD ANY PROPOSED TRANSFORMERS
 TO PLANS AND MAKE SURE SPACED ADEQUATELY FROM WATER
 SERVICES AND METERS.
  
 COMMENTS PER MIKE TECHNOW, CITY OF WPB PUBLIC UTILITIES
 - 561-494-1047 OR [email protected]:
  
 ADDITIONAL COMMENTS TO THE STANDARDS:
 -PER CORRESPONDENCE WITH THE CITY A CONSULTANT WILL BE
 RETAINED FOR DESIGN OF LIFT STATION.
 -INCLUDED LEVEL OF SERVICE CALCULATIONS. WILL NEED TO
 WORK WITH THE CITY TO OBTAIN UPDATED FLOW DATA.
 -MAINTAIN A MINIMUM HORIZONTAL SEPARATION OF 5? FROM
 TREE ROOT BARRIERS TO CITY OWNED UTILITIES. SHOW ON
 LANDSCAPING PLAN OR TYPICAL CROSS SECTION DETAIL.
 -CALL OUT UTILITY EASEMENTS.
 -CALL OUT HORIZONTAL SEPARATION FROM PROPOSED GRAVITY
 MAIN AND WATER MAIN. 5? MINIMUM FOR O.D. TO O.D.
 -CALL OUT FITTINGS AT CURVE.
 -SHOW PROPOSED/EXISTING DRY UTILITIES AND EASEMENTS.
 -CALL OUT TWO SINGLE SERVICES INSTEAD OF DOUBLE WITH
 SHARP ANGLE.
 -INCLUDE MINIMUM 10? UTILITY EASEMENT FOR PIPE NOT IN
 R/W.
 -FOR SEWER LATERALS EXCEEDING 75? WILL NEED ADDITIONAL
 CLEANOUT.
 -SHEET 5 MISSING UTILITY EASEMENT.
 -CALL OUT THE POINT OF SERVICE. PRIVATE SYSTEM FROM
 WHERE?
 -ON SHEET 3 PROVIDED ADDITION 10? GATE VALVE, CONSIDER
 DOUBLE VALVE AT CONNECTION TO EXISTING SYSTEM.
 -MAINTENANCE ACCESS TO CITY OWNED UTILITIES UNDER
 REVIEW.
 -PROPOSED WATER AND SEWER WILL COMPLY WITH THE LATEST
 REVISIONS TO STANDARDS AND SPECIFICATIONS.
  