| Date |
Text |
| 2022-01-19 13:02:29 | ENGINEERING |
| | |
| | CONDITION OF APPROVAL: -PROPOSED 3 INCH METER FOR 301 |
| | CLEMATIS ST. MUST BE INSTALLED ABOVE-GROUND IN |
| | CONFORMANCE TO WPB SD WS-3 SEP2019.-TWO MANHOLES IN |
| | ALLEY APPEAR TO BE OVERLAPPING ON CIVIL PLAN. PLEASE |
| | ENSURE MANHOLES HAVE ADEQUATE CLEARANCE DISTANCE. |
| | |
| | ALL OTHER COMMENTS SHALL BE ADDRESSED DURING FORMAL |
| | ENGINEERING SUBMITTAL. |
| | |
| | -WATER SERVICE SHOWN AT NORTH SIDE OF 300 BANYAN |
| | PROPERTY HAS NO EXISTING WATER METER INSTALLED. IF IT |
| | REMAINS AFTER BANYAN STREETSCAPE PROJECT WOULD HAVE TO |
| | COORDINATE METER INSTALLATION AND ACCOUNT SETUP WITH |
| | CITY WPB, AND PAY ALL APPLICABLE FEES, DEPOSITS, AND |
| | CHARGES. |
| | |
| | -PROPOSED METERED IRRIGATION WATER SERVICE AT NORTH |
| | SIDE OF PROPERTY DOES NOT SHOW PROPOSED BACKFLOW |
| | ASSEMBLY INSTALLATION. BACKFLOW ASSEMBLY WOULD HAVE TO |
| | BE INSTALLED FOR THE WATER SERVICE TO BE USED, AND MUST |
| | BE AT LOCATION APPROVED BY WPB PUBLIC UTILITIES. |
| | |
| | -VERTICAL MOUNT DCDA FIRELINE BACKFLOW ASSEMBLY IS |
| | NONSTANDARD. WOULD REQUIRE ENGINEER DESIGN AND |
| | EVALUATION. PROPOSED BACKFLOW ASSEMBLY MAKE/MODEL WOULD |
| | HAVE TO BE USC-APPROVED FOR VERTICAL ORIENTATION. |
| | |
| | -SITE PLAN SAYS FIRELINE BACKFLOW ASSEMBLY IS LOCATED |
| | IN AN OUTDOOR STORAGE ROOM AND APPEARS TO HAVE OPEN |
| | ENTRY. RECOMMEND VERIFYING LOCATION IS ACCEPTABLE TO |
| | FIRE DEPARTMENT AND MEETS NFPA STANDARDS. |
| | |
| | -SITE AND LANDSCAPING PLANS NEEDS TO BE UPDATED TO SHOW |
| | RELOCATION OF BIKE RACK NEAR THE WATER METER FOR 300 |
| | BANYAN AT SOUTH SIDE OF PROPERTY. CIVIL PLANS SHOW IT |
| | REMOVED ALRIGHT. (NOT SURE IF THEY SHOW THE NEW |
| | LOCATION) |
| | |
| | -PROPOSED 3 INCH BFP AND METER FOR 301 CLEMATIS ST. IS |
| | LOCATED SUBSTANTIALLY CLOSE TO EXISTING BUILDING. |
| | CONCERN WAS BROUGHT UP ABOUT BUILDING FOOTERS AND |
| | EXCAVATION ADJACENT BUILDING. EOR SUGGESTED DIMENSIONS |
| | OF BUILDING FOOTER AND SAFETY OF EXCAVATION COULD BE |
| | CONFIRMED. PLEASE SUBMIT THOSE VERIFICATIONS AT FORMAL |
| | ENGINEERING SUBMITTAL. |
| | |
| | |
| | -PROPOSED 3 INCH METERED WATER SERVICE FOR 301 CLEMATIS |
| | ST. IS NONSTANDARD DESIGN. MAY NEED REVISION AT FORMAL |
| | ENGINEERING SUBMITTAL. |
| | |
| | -PROPOSED 3 INCH BACKFLOW ASSEMBLY FOR 301 CLEMATIS ST. |
| | APPEARS TO BE IN THE RIGHT OF WAY. RECOMMEND VERIFYING |
| | LOCATION IS ACCEPTABLE WITH DEVELOPMENT SERVICES. |
| | |
| | -PLANS DO NOT SHOW EXISTING LARGE DIAMETER FIRELINE |
| | WATER SERVICE OR DCDA FIRELINE BACKFLOW INSTALLATION AT |
| | 301 CLEMATIS ST. SHOW BOTH AT FORMAL ENGINEERING |
| | SUBMITTAL. |
| | |
| | -PROPOSED 4 INCH PARALLEL RPZ MAY HAVE BIGGER FOOTPRINT |
| | THAN SHOWN ON CIVIL PLANS. |
| | |
| | -CIVIL PLANS DO NOT SHOW CROSSING INFORMATION OR |
| | PROFILES FOR UTILITY WORK IN ALLEY. WHEN REVIEWED AT |
| | FORMAL ENGINEERING SUBMITTAL, IF THERE ARE ANY |
| | CONFLICTS, ADDITIONAL WORK OR PLAN REVISION MAY BE |
| | NEEDED. |
| | |
| | -CIVIL PLANS DO NOT COMMUNICATE PROPOSED LOCATION FOR 2 |
| | INCH BFP AT EAST SIDE OF 301 CLEMATIS AND WHAT IS |
| | HAPPENING TO THE ASSOCIATED WATER METER. ANY PROPOSED |
| | LOCATION MUST BE REVIEWED BY PUBLIC UTILITIES AND |
| | RETEST/REINSPECTION WOULD BE REQUIRED. |
| | |
| | -CIVIL PLANS SHOW EXSS AND EXDN FLOWING TO ONE MANHOLE |
| | IN OLIVE. EOR NEEDS TO VERIFY IF THIS IS ACCURATE AND |
| | UPDATE PLANS AS NEEDED. |
| | |
| | -EXISTING METERED WATER SERVICES TO 301 CLEMATIS ST. |
| | BUILDING ARE NOT SHOWN AND LABELED ON WATER PLAN WITH |
| | WHAT IS HAPPENING TO THEM. UPDATE AT FORMAL ENGINEERING |
| | SUBMITTAL. |
| | |
| | -PLANS ARE MISSING SEVERAL STANDARD DETAILS INCLUDING |
| | SMALL METERED WATER SERVICE, LARGE METERED WATER |
| | SERVICE, AND FIRELINE BACKFLOW ASSEMBLY. ADD AT FORMAL |
| | ENGINEERING SUBMITTAL. |
| | |
| | -PLANS FOR EXISTING OVERHEAD UTILITIES AND UTILITY |
| | POLES ALONG THE ALLEYWAY WERE PREVIOUSLY UNCERTAIN. |
| | NEWEST REVISION PLANS STILL DO NOT SEEM TO ACCOUNT FOR |
| | THEM, OR DETAIL WHAT IS HAPPENING TO THEM. |
| | |
| |
Print |