Plan Review Notes
Plan Review Notes For Project Z21070018
Project Number Z21070018
Review Stop ENG - PPRC
Sequence Number 3
Notes
Date Text
2021-12-02 10:49:32COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., 561-494-1098 [email protected] :
  
 SHEET 6.1 & SHEET 6.2 ? LOOKS LIKE THESE SHEETS ARE
 INTENDED TO CONTAIN STANDARD DETAILS, BUT IT APPEARS
 LIKE THEY?RE FORMATTED WRONG. THE FILE NAME SHOWS CAD
 AND ALSO JPEG. PLEASE CORRECT.
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
 FOLLOWUP COMMENTS:
  
 SHOW AND LABEL PROPOSED METERED IRRIGATION WATER
 SERVICE AND BACKFLOW ASSEMBLY.
 RESPONSE: WE PLAN TO USE THE IRRIGATION METER THAT
 CURRENTLY EXISTS ON THE NORTH SIDE OF THE ALLEY AT THE
 300 BANYAN PROPERTY, BUT WILL CONFIRM PRIOR TO
 SUBMITTAL OF FORMAL ENGINEERING PERMITS.
 FOLLOWUP: METER BOX AND BACKFLOW ASSEMBLY NOT SHOWN
 CLEARLY ON PLANS, BUT MAY CONFLICT WITH THE LOADING
 ZONE. THEY CANNOT BE LOCATED IN VEHICULAR TRAFFIC.
  
 CIVIL PLANS DO NOT SHOW 301 CLEMATIS ST. PLEASE ADD
 SEPARATE SHEET SHOWING WATER AND SEWER UTILITY FOR THAT
 PROPERTY AND ADD WATER DEMAND CALCULATIONS. ALSO SHOW
 WATER AND SEWER SERVICES.
 RESPONSE: NO SITE CIVIL WORK IS BEING DONE FOR 301
 CLEMATIS. ADDING THIS TO THE PLAN SHEET WILL REQUIRE
 REDUCING THE DRAWING SCALE SIGNIFICANTLY. WE HAVE
 ELECTED TO SHOW THE 301 CLEMATIS PROPERTY ON A SEPARATE
 SHEET.
 NEW RESPONSE: BASED ON OWNER?S NEW PLANS, THE EXISTING
 2? WATER SERVICE AND BACKFLOW FROM OLIVE AVENUE TO 301
 CLEMATIS WILL BE ABANDONED, AND A NEW 3?
 SERVICE/BACKFLOW WILL BE BROUGHT IN FROM THE 4? WATER
 MAIN IN THE ALLEY. PLANS HAVE BEEN ADDED TO SHOW THE
 301 CLEMATIS BUILDING, SHOWING FIRE LINE ACCESS, WATER
 SERVICES, AND SEWER LINE CONNECTIONS. THIS DESIGN WILL
 BE FURTHER REFINED PRIOR TO FINAL PERMIT SUBMITTAL FOR
 ENGINEERING PERMITS.
 FOLLOWUP: SEPARATE SHEET FOR 301 CLEMATIS IS MISSING.
 PLEASE INCLUDE ON NEXT RESUBMITTAL. DESIGN OF PROPOSED
 WATER SERVICE FOR 301 CLEMATIS LOOKS PROBLEMATIC FOR
 SEVERAL REASONS. 3 INCH METER WOULD NOT BE ABLE TO BE
 PLACED AT SOUTH SIDE OF ALLEY ROW DUE TO VEHICLE
 TRAFFIC. THE OTHER SUBSTANTIAL ISSUES ARE THAT THE
 WATER SERVICE SHOULD NOT BE ROUTED THROUGH ANOTHER
 PRIVATE WATER SERVICE AND NOT SEEING ACCEPTABLE
 LOCATION FOR THE BACKFLOW ASSEMBLY. LESSER ISSUES ARE
 THAT PIPING IS SLEEVED, ADDITIONAL VALVING WOULD BE
 NEEDED, AND PIPE SIZING APPEARS INADEQUATE.
  
 NEW COMMENTS:
  
 -THERE APPEARS TO BE A BIKE RACK ON THE EAST SIDE OF
 THE DOMESTIC BACKFLOW ASSEMBLIES. THERE MAY NOT BE
 ENOUGH SPACE TO USE BIKE RACK SINCE THE BACKFLOWS AND
 METER ARE ABOVE-GROUND.
  
 -ON SIGNING PLAN PLEASE SHOW ANY SIGNS AT THE EAST SIDE
 OF THE ALLEY. THERE SHOULD BE SIGNS PREVENTING TRAFFIC
 INTO THE ALLEY AND ALSO SIGNS NOTIFYING OLIVE IS ONE
 WAY.
  
 -PLEASE ADJUST LOCATION OF ABOVE-GROUND METER SO THAT
 BYPASS BLOWOFF BOX WILL NOT BE RAN OVER BY VEHICLES IN
 ALLEY.
  
 -AUTOTURN EXHIBIT MAKES IT LOOK LIKE LARGE TRUCKS WILL
 HIT OBJECTS AND STRUCTURES IN ALLEY. PLEASE VERIFY
 LARGE VEHICLES WILL HAVE SUFFICIENT CLEARANCE.
  
 -PLANS DID NOT SHOW KNEE WALL ANYMORE AT SOUTH EAST
 OUTSIDE DINING AREA. A-1 SHEET MAKES TABLES LOOK CLOSE
 TO ALLEY TRAFFIC WITHOUT ANY OBJECTS IN BETWEEN FOR
 PROTECTION. IS THAT AS INTENDED?
  
 -ON GRADING PLAN PLEASE CHECK DRAINAGE AT THE 12.05
 ELEVATION IN ALLEY. WILL WATER FLOW INTO DINING AREA
 AND REMAIN THERE?
  
 -SHEETS 6.1 AND 6.2 OF CIVIL PLAN SET ARE NOT READABLE
 OR SHOWING CORRECTLY.
  
 -EXPLAIN WHAT IS HAPPENING TO THE EXISTING WATER
 SERVICE AND METER BOX ON THE NORTH SIDE OF THE PROPERTY
 ADJACENT BANYAN. IF IT WILL REMAIN, SHOW LOCATION ON
 PLANS.
  
  Print