| 2021-12-02 10:49:32 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG. |
| | SERVICES DEPT., 561-494-1098 [email protected] : |
| | |
| | SHEET 6.1 & SHEET 6.2 ? LOOKS LIKE THESE SHEETS ARE |
| | INTENDED TO CONTAIN STANDARD DETAILS, BUT IT APPEARS |
| | LIKE THEY?RE FORMATTED WRONG. THE FILE NAME SHOWS CAD |
| | AND ALSO JPEG. PLEASE CORRECT. |
| | |
| | COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR |
| | [email protected]: |
| | FOLLOWUP COMMENTS: |
| | |
| | SHOW AND LABEL PROPOSED METERED IRRIGATION WATER |
| | SERVICE AND BACKFLOW ASSEMBLY. |
| | RESPONSE: WE PLAN TO USE THE IRRIGATION METER THAT |
| | CURRENTLY EXISTS ON THE NORTH SIDE OF THE ALLEY AT THE |
| | 300 BANYAN PROPERTY, BUT WILL CONFIRM PRIOR TO |
| | SUBMITTAL OF FORMAL ENGINEERING PERMITS. |
| | FOLLOWUP: METER BOX AND BACKFLOW ASSEMBLY NOT SHOWN |
| | CLEARLY ON PLANS, BUT MAY CONFLICT WITH THE LOADING |
| | ZONE. THEY CANNOT BE LOCATED IN VEHICULAR TRAFFIC. |
| | |
| | CIVIL PLANS DO NOT SHOW 301 CLEMATIS ST. PLEASE ADD |
| | SEPARATE SHEET SHOWING WATER AND SEWER UTILITY FOR THAT |
| | PROPERTY AND ADD WATER DEMAND CALCULATIONS. ALSO SHOW |
| | WATER AND SEWER SERVICES. |
| | RESPONSE: NO SITE CIVIL WORK IS BEING DONE FOR 301 |
| | CLEMATIS. ADDING THIS TO THE PLAN SHEET WILL REQUIRE |
| | REDUCING THE DRAWING SCALE SIGNIFICANTLY. WE HAVE |
| | ELECTED TO SHOW THE 301 CLEMATIS PROPERTY ON A SEPARATE |
| | SHEET. |
| | NEW RESPONSE: BASED ON OWNER?S NEW PLANS, THE EXISTING |
| | 2? WATER SERVICE AND BACKFLOW FROM OLIVE AVENUE TO 301 |
| | CLEMATIS WILL BE ABANDONED, AND A NEW 3? |
| | SERVICE/BACKFLOW WILL BE BROUGHT IN FROM THE 4? WATER |
| | MAIN IN THE ALLEY. PLANS HAVE BEEN ADDED TO SHOW THE |
| | 301 CLEMATIS BUILDING, SHOWING FIRE LINE ACCESS, WATER |
| | SERVICES, AND SEWER LINE CONNECTIONS. THIS DESIGN WILL |
| | BE FURTHER REFINED PRIOR TO FINAL PERMIT SUBMITTAL FOR |
| | ENGINEERING PERMITS. |
| | FOLLOWUP: SEPARATE SHEET FOR 301 CLEMATIS IS MISSING. |
| | PLEASE INCLUDE ON NEXT RESUBMITTAL. DESIGN OF PROPOSED |
| | WATER SERVICE FOR 301 CLEMATIS LOOKS PROBLEMATIC FOR |
| | SEVERAL REASONS. 3 INCH METER WOULD NOT BE ABLE TO BE |
| | PLACED AT SOUTH SIDE OF ALLEY ROW DUE TO VEHICLE |
| | TRAFFIC. THE OTHER SUBSTANTIAL ISSUES ARE THAT THE |
| | WATER SERVICE SHOULD NOT BE ROUTED THROUGH ANOTHER |
| | PRIVATE WATER SERVICE AND NOT SEEING ACCEPTABLE |
| | LOCATION FOR THE BACKFLOW ASSEMBLY. LESSER ISSUES ARE |
| | THAT PIPING IS SLEEVED, ADDITIONAL VALVING WOULD BE |
| | NEEDED, AND PIPE SIZING APPEARS INADEQUATE. |
| | |
| | NEW COMMENTS: |
| | |
| | -THERE APPEARS TO BE A BIKE RACK ON THE EAST SIDE OF |
| | THE DOMESTIC BACKFLOW ASSEMBLIES. THERE MAY NOT BE |
| | ENOUGH SPACE TO USE BIKE RACK SINCE THE BACKFLOWS AND |
| | METER ARE ABOVE-GROUND. |
| | |
| | -ON SIGNING PLAN PLEASE SHOW ANY SIGNS AT THE EAST SIDE |
| | OF THE ALLEY. THERE SHOULD BE SIGNS PREVENTING TRAFFIC |
| | INTO THE ALLEY AND ALSO SIGNS NOTIFYING OLIVE IS ONE |
| | WAY. |
| | |
| | -PLEASE ADJUST LOCATION OF ABOVE-GROUND METER SO THAT |
| | BYPASS BLOWOFF BOX WILL NOT BE RAN OVER BY VEHICLES IN |
| | ALLEY. |
| | |
| | -AUTOTURN EXHIBIT MAKES IT LOOK LIKE LARGE TRUCKS WILL |
| | HIT OBJECTS AND STRUCTURES IN ALLEY. PLEASE VERIFY |
| | LARGE VEHICLES WILL HAVE SUFFICIENT CLEARANCE. |
| | |
| | -PLANS DID NOT SHOW KNEE WALL ANYMORE AT SOUTH EAST |
| | OUTSIDE DINING AREA. A-1 SHEET MAKES TABLES LOOK CLOSE |
| | TO ALLEY TRAFFIC WITHOUT ANY OBJECTS IN BETWEEN FOR |
| | PROTECTION. IS THAT AS INTENDED? |
| | |
| | -ON GRADING PLAN PLEASE CHECK DRAINAGE AT THE 12.05 |
| | ELEVATION IN ALLEY. WILL WATER FLOW INTO DINING AREA |
| | AND REMAIN THERE? |
| | |
| | -SHEETS 6.1 AND 6.2 OF CIVIL PLAN SET ARE NOT READABLE |
| | OR SHOWING CORRECTLY. |
| | |
| | -EXPLAIN WHAT IS HAPPENING TO THE EXISTING WATER |
| | SERVICE AND METER BOX ON THE NORTH SIDE OF THE PROPERTY |
| | ADJACENT BANYAN. IF IT WILL REMAIN, SHOW LOCATION ON |
| | PLANS. |
| | |
| |