Plan Review Notes
Plan Review Notes For Project Z21070018
Project Number Z21070018
Review Stop PU
Sequence Number 1
Notes
Date Text
2022-01-21 19:50:35COMMENTS FOR THE REFERENCED PROJECT:
  
 -SHOW EXISTING UNDERGROUND UTILITIES ON OLIVE AVE AND
 IN THE ALLEY.
 -ADD NOTE/CALL OUT PROPOSED AND EXISTING UTILITY
 CONFLICTS WITH ELEVATIONS.
 -PROFILE OF PROPOSED SERVICE LINES SHOWING ELEVATIONS
 AND CONFLICTS FROM TAP TO POINT OF SERVICE WILL BE
 REQUIRED.
 - ADD NOTE THAT WATER MAIN TIE-IN IS TO PROCEED AFTER
 THE CONTRACTOR HAS SUBMITTED A CONSTRUCTION PHASING
 PLAN FOR PIGGING/FLUSHING TO THE CITY AND RECEIVING PBC
 HEALTH DEPARTMENT APPROVAL.
 -INSERT COWPB STANDARD DETAIL GS-7 ?DOGHOUSE MANHOLE?
 ON DETAIL SHEET.
 -THE GRAVITY SEWER IS REQUIRED TO HAVE A CASING THROUGH
 THE CONFLICT MANHOLE. INSERT COWPB STANDARD DETAIL P-10
 FOR THE CASING AND THE FDOT CONFLICT MANHOLE STANDARD
 DETAIL INDEX 425-080 INTO THE PLANS.
  