2021-12-02 10:54:03COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., 561-494-1098 [email protected] :
  
 1. PLEASE CLARIFY RESPONSE TO REQUEST FOR CCTV OF
 SANITARY AND STORM. COMPLETION OF WHAT? PROVISION OF
 CCTV IS A CONDITION OF SITE PLAN APPROVAL AS PREVIOUSLY
 STATED.
 2. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX). PLEASE PROVIDE YOUR CONTACT INFORMATION
 WITH RESPONSE.
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
 FOLLOWUP COMMENTS:
  
 COMMENT 2: 12. WILL ALL OF THE METERED PARKING SPOTS ON
 DATURA REMAIN AFTER PROJECT COMPLETED? RESPONSE: A
 PORTION OF THE METERED PARKING WILL BE REMOVED DUE TO
 REDESIGN OF DATURA STREET LAYOUT. EMAIL SEAN SAMUELS
 [email protected] AND COPY DANIEL GIUST [email protected]
 AND ANA MARIA APONTE [email protected] REGARDING THIS
 ISSUE.
 RESPONSE 2: TRANSPORTATION ENGINEER TO ANSWER.
 FOLLOWUP: NOT SATISIFIED. SEAN SAMUELS ADVISED STILL
 NEED TO CONTACT HIM AS THERE ARE DETAILS TO WORK OUT.
 EMAIL SEAN SAMUELS [email protected] AND COPY DANIEL
 GIUST [email protected] AND ANA MARIA APONTE
 [email protected] REGARDING THIS ISSUE.
  
  
 NEW COMMENTS:
  
 -4 BY 6 METER VAULT CANNOT BE USED. LARGE DOMESTIC
 METERS SIZED 3 INCH OR GREATER MUST BE INSTALLED ABOVE
 GROUND. REVISE LABEL WORDING OF WATER METER TO INDICATE
 SIZING AND ABOVE GROUND INSTALLATION. INCLUDE THAT
 WATER SERVICE STANDARD DETAIL ON A SEPARATE SHEET.
  
 -ON SEPARATE SHEET WITH CIVIL PLANS INCLUDE ADDITIONAL
 STANDARD DETAILS INCLUDING SMALL BACKFLOW ASSEMBLY,
 LARGE BACKFLOW ASSEMBLY, SMALL METERED WATER SERVICE,
 FIRELINE DCDA, AND PAVEMENT RESTORATION.
  
 -FIRELINE BACKFLOW ASSEMBLY SHOULD NOT BE IN UTILITY
 EASEMENT. LIKELY WOULD NEED TO ADJUST BOUNDARY OF
 UTILITY EASEMENT.
  
 -IRRIGATION BACKFLOW ASSEMBLY MAY NOT BE LOCATED IN THE
 RIGHT OF WAY. MUST BE ON PRIVATE PROPERTY. WOULD NEED
 TO BE IMMEDIATELY AFTER SIDEWALK SOUTH OF THE METER
 BOX.
  
 -WILL THERE BE SIGNAGE TO PREVENT DRIVERS FROM ENTERING
 EXIT ONLY DRIVEWAY?
  
 -PLEASE LABEL ALL OF THE WATER SERVICES AND SEWER
 LATERALS EXISTING OR PROPOSED.
  
 -CIVIL PLANS DO NOT SHOW SEVERAL EXISTING WATER
 SERVICES ALONG DATURA ST THAT WOULD REQUIRE REMOVAL.
 SHOW THOSE CLEARLY AT FORMAL ENGINEERING SUBMITTAL.
  
 -APPLICANT MUST PAY ANY UTILITY FEES, CHARGES, OR
 DEPOSITS REQUIRED BY CITY OF WPB UTILITIES.
  
 -AT FORMAL ENGINEERING SUBMITTAL: ADD FIRE FLOW
 CALCULATIONS TO WATER PLAN, ADD PROFILES OF WATER
 SERVICES, ADD CROSSING INFORMATION, LABEL ALL WATER AND
 SEWER UTILITIES WITH PIPE SIZE AND MATERIAL TYPE, ADD
 SLOPE GUIDANCE TO SEWER LATERALS, ADD ELEVATION INFO TO
 SEWER MANHOLES.
  