Plan Review Notes
Plan Review Notes For Project Z21070016
Project Number Z21070016
Review Stop Z
Sequence Number 2
Notes
Date Text
2021-09-17 14:33:39SUBMISSION #1 COMMENTS
  
 SETBACKS
 1. [SATISFIED] BOTH DATURA STREET AND QUADRILLE PLAZA
 DRIVE ARE BOTH CLASSIFIED AS PRIMARY PEDESTRIAN
 STREETS, PLEASE NOTE/MAKE ADJUSTMENTS AS NECESSARY
 (PROPOSED PLANS SHOW AS SECONDARY & AVENUE).
 2. [PARTIALLY SATISFIED] SETBACK IS MEASURED FROM THE
 PROMINENT CURB-LINE LOCATION (+50% OF FRONTAGE)
 LANDSCAPE PLANS INCORRECTLY LABEL THE BACK OF CURB
 ALONG DATURA STREET, SITE PLAN SHOWS BACK OF CURB
 COINCIDING WITH THE ON STREET PARKING SPACE.
  
 OPEN SPACE
 3. [PARTIALLY SATISFIED] PLEASE PROVIDE INFORMATION ON
 PRIVATE OPEN SPACE (SEC. 94-109 TABLE IV-7), SPECIFYING
 THE AMOUNT, LOCATION, AND TYPE OF SPACE. CONFIRM
 COMPLIANCE WITH STANDARDS LOCATED IN TABLE FOR EACH
 TYPE OF SPACE.
 PROJECT COMPLIES WITH THE PRIVATE OPEN SPACE
 REQUIREMENTS WITH THE 7TH FLOOR TERRACE AND ROOFTOP
 GARDEN ON THE 19TH FLOOR. PLEASE REMOVE THE GROUND
 FLOOR PRIVATE OPEN SPACE DIAGRAM AND CALCULATIONS, AS
 THE GROUND FLOOR AREAS SHOWN WOULD NOT MEET THE CODE
 REQUIREMENTS OR CONSTITUTE AS A PRIVATE/PUBLIC OPEN
 SPACE.
  
 ACTIVE USE
 4. [NOT SATISFIED] PROPOSED PROJECT IS NOT IN
 COMPLIANCE WITH MINIMUM GROUND ACTIVE USES (65%) ALONG
 PRIMARY PEDESTRIAN STREETS (DATURA). SEE TABLE IV-42
 BUILDING REQUIREMENTS QBD 10-25.
 VARIANCE IS BEING SOUGHT TO REDUCE ACTIVE USE
 REQUIREMENT FROM 65% TO 30%, WARRANTS ADDITIONAL
 DISCUSSION W/ STAFF.
 5. [NOT SATISFIED] PROPOSED PROJECT IS NOT IN
 COMPLIANCE WITH MINIMUM LINER ACTIVE USES [2 TO 5
 STORIES (80?)] WHICH REQUIRES 60% ALONG PRIMARY
 PEDESTRIAN STREETS (DATURA).
 VARIANCE IS BEING SOUGHT TO REDUCE ACTIVE USE LINER
 REQUIREMENT FROM FLOORS 2 TO 5, FROM 60% TO X%,
 WARRANTS ADDITIONAL DISCUSSION W/ STAFF.
  
 STREETSCAPE
 6. [NOT SATISFIED] PLEASE PROVIDE PHOTOMETRIC PLAN FOR
 THE SITE. PHOTOMETRIC PLAN IS PROVIDED, HOWEVER PROJECT
 SITE PHOTOMETRICS ARE NOT IN COMPLIANCE WITH CODE.
 REQUIRED MINIMUM OF 0.6 FOOT CANDLES AS MEASURED AT THE
 BACK EDGE OF THE CURB AND ONE FOOT ABOVE THE SIDEWALK.
 A)[PARTIALLY SATISFIED] SPECIFY THE LIGHT FIXTURE
 SPECS. MAKE SURE PROPOSED FIXTURES ARE IN COMPLIANCE
 WITH THE CITY STANDARDS.
 CITY/DMP LIGHTNING SPECS REQUIRE 13 FT. POLES WITH BOTH
 THE POLES AND LIGHT FIXTURES BEING BLACK IN COLOR.
 ADHERE TO DOWNTOWN STANDARD ALONG DATURA. DECORATIVE
 FIXTURES ALONG QUADRILLE PLAZA SHALL MATCH EXISTING
 FIXTURES INSTALLED IN FRONT OF STATION.
  
 7. [NOT SATISFIED] PROVIDE LANDSCAPE PLAN WITH STREET
 TREES ALONG QUADRILLE PLAZA DRIVE AND DATURA STREET,
 NEXT TO CURB. (SEC. 94-113)
 STREET TREES SHALL BE PLANTED AND SPACED EVERY 30 FT.
 ALONG ENTIRE FRONTAGE. TREE PLACEMENT SHALL BE AS CLOSE
 TO THE CURB AS POSSIBLE. RECOMMEND SEPARATE MEETING
 WITH STAFF TO DISCUSS LANDSCAPE/STREETSCAPE CHANGES
 ALONG QUADRILLE PLAZA DR. AND DATURA ST.
 8. [SATISFIED] GREASE TRAP NOT PERMITTED ON SIDEWALK.
  
 BIKES, PARKING, & LOADING
 9. AS PER ARTICLE IV: SEC. 94-111, BICYCLE PARKING MUST
 INCLUDE:
 A) [SATISFIED] (I) SECURE BIKE RACKS AND/OR STORAGE AT
 A RATIO OF ONE BICYCLE PARKING SPACE PER EVERY 15
 PARKING SPACES PROVIDED
 B) [SATISFIED] FOR HOTEL (II) A MINIMUM OF ONE SHOWER
 AND CHANGING FACILITY SHALL BE PROVIDED TO BE AVAILABLE
 FOR ALL TENANTS AND SHALL BE LOCATED WITHIN THE
 BUILDING, OR WITHIN 200 FEET OF THE BUILDING ENTRANCE,
 FOR DEVELOPMENTS GREATER THAN 50,000 SQUARE FEET IN
 GROSS BUILDING AREA. PLEASE INDICATE THE LOCATION OF
 SHOWER FACILITIES.
 C) [NOT SATISFIED] ADDITIONALLY, 1 SPACE PER 100 FT. OF
 STREET FRONTAGE; TO BE LOCATED ALONG ROW OR STREET
 FRONTAGES FOR PUBLIC ACCESS.
 PLEASE PROVIDE 4 ADDITIONAL BIKE RACKS WITHIN THE
 PUBLIC ROW. PLEASE INCLUDE A HARDSCAPE PLAN INCLUDING
 ALL ELEMENTS ALONG THE STREETSCAPE.
 D) [SATISFIED] PLEASE SEPARATE HOTEL/COMMERCIAL USE
 BIKE PARKING FROM THE RESIDENTIAL USE BIKE PARKING
 10. PLEASE INCLUDE TABLE OF PARKING REQUIREMENTS
 A) [PARTIALLY SATISFIED] EXPLAIN IF PARKING IS COMBINED
 BETWEEN USES OR IF USE WILL HAVE SEGREGATED SPACES.
 PLEASE INDICATE IF THE PARKING FOR RESIDENTIAL AND
 HOTEL USES ARE COMMON POOL OR IF THEY ARE RESERVED
 SPACES. ADDITIONALLY, PLEASE LABEL THE SPACES FOR BOTH
 COMMERCIAL AND GUEST PARKING.
 B)[PARTIALLY SATISFIED] # OF SPACES REQUIRED PER USE &
 # OF SPACES PROVIDED
 SEE ABOVE COMMENT.
 C) [SATISFIED] PARKING DETAIL/STRIPING IS NOT TO THE
 CITY STANDARDS, PLEASE UPDATE.
 11. [PARTIALLY SATISFIED] SPECIFY AUTOTURN AND SERVICE
 ACCESS/LOADING FOR THE SITE.
 PLEASE INCLUDE WITHIN SITE PLAN, GROUND FLOOR PLAN, OR
 SEPARATE ARCHITECTURAL PLAN.
  
  
 FACADE ARTICULATION
 12. [PARTIALLY SATISFIED] ARTIFICIAL GREENERY/MATERIALS
 OR ELEMENTS ARE NOT PERMITTED ON THE FACADE/VISIBLE
 FROM THE ROW.
 PLEASE PROVIDE ADDITIONAL DETAILS OF THE PROPOSED
 VERTICAL VEGETATION SYSTEM.
 13. [SATISFIED] PLANAR BREAKS NOT IN COMPLIANCE WITH
 CODE. SEC. 94-109 TABLE IV-4
 A) [SATISFIED] PLANAR BREAKS B AND D (17% OF FRONTAGE
 COMBINED) DOES NOT MEET THE MINIMUM STANDARD OF 20% OF
 BUILDING FRONTAGE.
  
 GENERAL SITE
 14. PROVIDE SITE TABLE WITH:
 A) [PARTIALLY SATISFIED] SITE AREA
 PLEASE ADDRESS THE DISCREPANCY BETWEEN THE GROSS
 BUILDING AREA (GBA) AND FLOOR AREA RATIO (FAR) VALUES
 BETWEEN SHEETS A-0.03 (231,228 SF) AND A-0.04 (232,370
 SF), THE OVERALL AREA VALUE SHALL BE THE SAME.
 B) [PARTIALLY SATISFIED] GROSS BUILDING AREA ALLOWED
 SEE ABOVE COMMENT.
 C) [PARTIALLY SATISFIED] GROSS BUILDING AREA PROPOSED
 GROUND FLOOR GBA CALCULATION AND DIAGRAMS SHALL INCLUDE
 THE VALET ROOM, AND ASSOCIATED BIKE ROOM
 SHOWER/BATHROOM AREA.
 D) [SATISFIED] TDRS NEEDED FOR PROJECT.
 DAC APPROVAL WILL BE REQUIRED BEFORE ISSUANCE OF
 BUILDING PERMIT.
 15. [SATISFIED] PLEASE CONFIRM THAT GROSS BUILDING AREA
 CALCULATIONS ARE MEASURED FROM THE EXTERIOR WALL.
 16. [SATISFIED] CHANGES ON THE FACADE ELEVATIONS ALONG
 THE 2ND FLOOR DOES NOT SEEM TO REFLECT THE FLOOR PLANS.
 17. [SATISFIED] INDICATE ALLEYWAY IS ONE-WAY GOING
 EAST.
 18. [NOT SATISFIED] FDC SHALL BE WALL MOUNTED.
 FDC NOT SHOWN AS WALL MOUNTED ON SHEET A-2.01,
 ADDITIONALLY LP-1.01 IS NOT UPDATED AND SHOWS FDC AND
 DDAC ON FRONTAGE BEHIND LANDSCAPE SCREENING. PLEASE
 CLARIFY WHAT THE BOX IS NEXT TO THESE ELEMENTS, IS THIS
 A TRANSFORMER? FDC SHALL BE WALL MOUNTED IF ALLOWED BY
 FD.
 19. [PARTIALLY SATISFIED] DDCV SHALL NOT BE LOCATED
 WITHIN MINIMUM SETBACK.
 RELOCATE WATER METER AND DDCA TO THE WEST SIDE OF THE
 BUILDING.
 20. [SATISFIED] CONFIRM THE AMOUNT OF OPENINGS IN
 GARAGE WEST ELEVATION COMPLIES WITH FIRE CODE.
  
 ADDITIONAL COMMENTS BASED ON RESUBMITTED DRAWINGS AND
 DOCUMENTS 9/17/21:
  
 1. PROPOSED VALET STACKING DOES NOT WORK WITH THE
 90-DEGREE PARKING CONFIGURATION, THE PROPOSED SPACE FOR
 PARKING ALONG DATURA MAY BE ALLOCATED OR CONVERTED INTO
 A GROUND FLOOR ACTIVE USE. THUS ELIMINATING OR REDUCING
 THE VARIANCE REQUIRED FOR ACTIVE USES ALONG DATURA
 STREET.
  
 2. PLEASE INCLUDE A HARDSCAPE PLAN THAT INCLUDES ALL
 ELEMENTS ALONG THE STREETSCAPE.
  
 3. PLEASE INCLUDE EXHIBIT WITH EXISTING ON STREET
 PARKING SPACE AND PROPOSED SPACES. IF EXISTING
 ON-STREET PARKING IS REMOVED, A REMOVAL FEE WILL BE
 ASSESSED.
  
 4. PLEASE INCLUDE THE CURB AND BUILDING ON THE SOUTH
 SIDE OF THE ALLEY AND WEST SIDE OF PROJECT, WITHIN BOTH
 THE SITE PLAN AND GROUND FLOOR PLAN.
  
 5. PLEASE EXPLAIN THE CHANGES TO THE CURB WEST OF THE
 BUILDING ON DATURA STREET.
  
 6. PROPOSED ON STREET PARKING CAN BE REDUCED TO 20 FT.
 LONG (ALONG QUADRILLE PLAZA DRIVE)
  
 7. PLEASE CLEARLY INDICATE CHANGES ON THE CURB LOCATION
 ON QUADRILLE PLAZA DRIVE, PLEASE SHOW THE EAST SIDE OF
 THE ROAD ON THE CIVIL DRAWINGS AND SITE PLAN. THE SAME
 FOR DATURA STREET.
  
 8. PLEASE ALSO PROVIDE SECTION FOR QUADRILLE PLAZA
 DRIVE FRONTAGE AS IS ILLUSTRATED IN CP100 OR CP101.
  
 9. PLEASE INCLUDE DETAILS OF THE GARAGE SCREENING THAT
 IS PROPOSED, BEYOND THE MATERIAL PICTURE ON ELEVATION
 SHEETS.
  
 10. ON ELEVATIONS PLEASE PROVIDE PROJECTION OF PROPERTY
 LINES AND MINIMUM SETBACK LINES TO DETERMINE
 ENCROACHMENTS OR AERIAL EASEMENTS.
  
 11. RECOMMEND SEPARATE MEETING WITH STAFF TO DISCUSS
 LANDSCAPE CHANGES AND ACTIVE LINER USE/GROUND FLOOR USE
 ALONG DATURA ST.
  
 12. FOR DAC SUBMITTAL PLEASE PROVIDE COLOR ELEVATIONS
 INSERTED INTO CONTEXT AND RENDERINGS OF THE PROPOSED
 PROJECT FROM QUADRILLE AND DATURA.
  
 13. RESUBMIT FOR DAC ON THE 24TH FOR THE NOVEMBER
 MEETING.
  