Plan Review Notes
Plan Review Notes For Project Z21070016
Project Number Z21070016
Review Stop PU
Sequence Number 2
Notes
Date Text
2022-01-11 10:21:36-LEVEL OF SERVICE CALCULATIONS
 - PLEASE ADD NOTE THAT THIS IS WITHIN LS 21 SERVICE
 AREA.
 -NOTE TO CUT AND CAP UNUSED SERVICES AT THE MAIN.
 -PROVIDE PROFILE OF SERVICE CONNECTIONS FROM TAP TO
 POINT OF SERVICE.
 -SHOW/CALL OUT UTILITY CONFLICTS.
 -CALL OUT SIZE OF GAS MAIN.
 -CALL OUT HORIZONTAL SEPARATION BETWEEN CITY UTILITIES
 AND EXISTING UNDERGROUND UTILITIES.
 -PROVIDE NAVD CONVERSION ON THE SCALE.
 -SHOW ALL EXISTING DRY UTILITIES.
 -WHAT SIZE IS THE GREASE TRAP CONNECTION?
 -PLEASE SHOW ALL VALVES, SHOW PIPE TYPE AND SIZE.
  
 CONTACT MIKE TECHNOW AT [email protected] WITH ANY
 QUESTIONS
  