Plan Review Notes
Plan Review Notes For Project Z21070016
Project Number Z21070016
Review Stop STORM
Sequence Number 1
Notes
Date Text
2021-08-12 09:29:16THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY'S OFFICIAL VERTICAL DATUM PER CITY CODE IS
 NGVD1929. THE CITY IS ALLOWING SURVEYS AND PLANS TO USE
 NAVD1988 PROVIDED THE CONVERSION EQUATION BETWEEN
 NAVD1988 AND NGVD1929 IS ALSO PROVIDED. PROVIDE THE
 CONVERSION EQUATION TO NGVD1929 ON THE SURVEYS.
  
 2. LABEL THE VERTICAL DATUM AND PROVIDED THE CONVERSION
 EQUATION TO NGVD1929 WHEN ELEVATIONS ARE ADDED TO THE
 ENGINEERING PLANS.
  
 3. THE EXISTING DRAINAGE SYSTEM ON DATURA STREET IS
 AFFECTED BY THE PROPOSED CURBED BULBOUTS. SHOW HOW THE
 SYSTEM WILL BE MODIFIED.
  
 4. PROVIDE TYPICAL CROSS SECTIONS FROM CENTERLINE OF
 STREET TO FACE OF BUILDING. SHOW AND DIMENSION THE
 RIGHT OF WAY FROM THE BACK OF SIDEWALK.
  
 5. PROVIDE A CROSS SECTION OF THE ALLEY FROM FACE OF
 THE BUILDING ON THE SOUTH SIDE OF THE ALLEY TO THE FACE
 OF THE PROPOSED BUILDING. SHOW GRADE BREAKS AND
 DIMENSIONS TO MAJOR FEATURES (R/W, C&G, BUILDING FACE,
 SIDEWALK, ETC.)
  
 6. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA FOR WATER QUALITY TREATMENT AND PEAK FLOW.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE COPY OF SFWMD ERP PERMIT(S) BEFORE START OF
 CONSTRUCTION.
  
 4. PROVIDE A COPY OF THE DRAINAGE CALCULATIONS WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  
  