| Date |
Text |
| 2021-08-05 13:06:23 | COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, |
| | ENGINEERING SERVICES DEPT., 561-494-1098 |
| | [email protected] : |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF |
| | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY |
| | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND |
| | WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW |
| | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER |
| | ENGINEERING RELATED DOCUMENTS, CLICK HERE OR GO TO: HTT |
| | PS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-FOR |
| | MS-PERMITS-AND-APPLICATIONS . |
| | 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH, |
| | FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED |
| | SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90 |
| | UTILITIES, ARTICLE I. SEC. 90-7. |
| | POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE |
| | FACILITIES OF THE CITY: |
| | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE |
| | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY |
| | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, |
| | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. |
| | 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| | MORE INFORMATION, CLICK HERE OR GO TO: HTTPS://WWW.WPB. |
| | ORG/GOVERNMENT/ENGINEERING/ENGINEERING-FORMS-PERMITS-AN |
| | D-APPLICATIONS . |
| | 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY |
| | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC |
| | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF |
| | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| | [email protected] OR 561-494-1040 FOR FURTHER |
| | ASSISTANCE. |
| | 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS |
| | OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, |
| | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND |
| | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, |
| | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE |
| | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING |
| | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, |
| | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL |
| | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER |
| | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN |
| | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. |
| | PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT |
| | MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL |
| | EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT, |
| | INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES LOCATED ON THE |
| | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL |
| | UTILITY CROSSINGS. |
| | 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY |
| | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY |
| | ROW. |
| | 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE |
| | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB |
| | DEVELOPMENT APPLICATION). |
| | 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND |
| | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM |
| | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE |
| | PER FAC 64E-8 FOR WATER AND PER FAC 64-E.008 FOR SEWER. |
| | 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION |
| | (NAVD 88 AND NGVD 29). |
| | 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND |
| | STORMWATER ALONG ENTIRE PROJECT FRONTAGE. |
| | 11. PLEASE ADD NOTE TO PLANS SPECIFYING CITY?S |
| | DOWNSTREAM LIFT STATION NUMBER. |
| | 12. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND |
| | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED |
| | AREAS. |
| | 13. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR |
| | PROPOSED SANITARY LATERALS. |
| | 14. PLEASE LABEL WATER LINES AS PRIVATE WHERE |
| | APPLICABLE. |
| | 15. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED |
| | LOCATION OF WATER METER AND BACKFLOW PREVENTION. |
| | 16. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING |
| | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT |
| | HIM AT 561-494-2262 OR [email protected] |
| | 17. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS |
| | FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS. |
| | |
| | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, |
| | PLEASE CONTACT 561-494-2262 OR [email protected]: |
| | |
| | -VERIFY WITH WPB FIRE MARSHAL THAT PROPOSED DCDA |
| | LOCATION IS ACCEPTABLE. |
| | |
| | -SEPARATE THE FIRELINE FROM THE DOMESTIC WATER SERVICE |
| | WITH ITS OWN PIPING FROM THE WATER MAIN. |
| | |
| | -DOMESTIC WATER METER FOOTPRINT ON UTILITY PLAN LOOKS |
| | SUBSTANTIALLY SMALLER THAN A TYPICAL LARGE METERED |
| | WATER SERVICE. |
| | |
| | -METERS THREE INCHES OR LARGER NEED TO BE INSTALLED |
| | ABOVE-GROUND AND OUTSIDE OF BUILDING. |
| | |
| | -DOMESTIC BACKFLOW ASSEMBLIES NEED TO BE INSTALLED |
| | OUTSIDE OF BUILDING. SHOW AND LABEL THEM ON THE UTILITY |
| | PLAN. |
| | |
| | -CONSIDER DUAL/PARALLEL DOMESTIC BACKFLOW ASSEMBLIES TO |
| | MINIMIZE WATER OUTAGES DURING BACKFLOW MAINTENANCE. |
| | |
| | -WILL A SEPARATE METERED IRRIGATION WATER SERVICE BE |
| | NEEDED? |
| | |
| | -THERE IS A CLEANOUT IN ALLEY WHERE DOORS OPEN WHICH |
| | MAY CONFLICT WITH USE OF EACH AT THE SAME TIME. |
| | |
| | -ADD WATER DEMAND CALCULATIONS TO UTILITY PLAN. |
| | |
| | -IF THERE WILL BE DEMOLITION, DEMOLITION PLAN NEEDS TO |
| | BE SUBMITTED. |
| | |
| | -ALLEY IS ONE-WAY FROM WEST TO EAST. IT IS ALSO NARROW |
| | AT BOTH ENDS AND THERE MAY BE SOME POLES AND BOLLARDS |
| | THROUGHOUT. CAN PROPOSED LOADING DOCK BE UTILIZED BY |
| | THE NEEDED VEHICLES BASED ON THAT INFORMATION? |
| | |
| | -WILL ALL OF THE METERED PARKING SPOTS ON DATURA REMAIN |
| | AFTER PROJECT COMPLETED? |
| | |
| | -HISTORIC PICTURES AND SURVEY SHOW TALL UTILITY POLE IN |
| | ALLEY ADJACENT SOUTH PROPERTY LINE. PLEASE SHOW AND |
| | LABEL ON UTILITY PLAN. |
| | |
| | -FIBER OPTIC BOX IN ALLEY NOT SHOWING ON UTILITY PLAN. |
| | PLEASE ADD AND LABEL. DO SAME WITH ELECTRIC VAULT. |
| | |
| | -WATER MAINS AND/OR SEWER MAINS MAY NEED TO BE REPLACED |
| | BY APPLICANT TO FACILITATE PROPOSED SEWER LATERALS AND |
| | WATER SERVICES. |
| | |
| | -ON UTILITY PLAN PLEASE SHOW THE BOLLARDS, DCDA, AND |
| | STREET SIGNS IN ALLEY. |
| | |
| | -LABEL THE FIRE HYDRANT NEAR SOUTHEAST AREA OF PROPERTY |
| | TO THE UTILITY PLAN. |
| | |
| | -SOME OF THE BUILDING STRUCTURES APPEAR TO BE THE IN |
| | THE SETBACKS. IS THAT ALLOWED? |
| | |
| | -ON THE SITE PLAN AND UTILITY PLAN, PLEASE LABEL THE |
| | TWO OBJECTS JUST NORTH OF THE PUMP ROOM. |
| | |
| | -LANDSCAPING PLAN ONLY SHOWS TREES BEING REMOVED. |
| | PLEASE UPDATE LANDSCAPING PLAN TO SHOW ANY OTHER |
| | PROPOSED OR EXISTING LANDSCAPING SUCH AS TREES, BUSHES, |
| | PLANTS, AND GRASS. VERIFY TREES WILL NOT CONFLICT WITH |
| | UTILITIES. ALSO ADD SEPARATE SHEET SHOWING UTILITIES |
| | OVERLAID WITH LANDSCAPING. |
| | |
| | COMMENTS PER MIKE TECHNOW 561-494-1047 OR |
| | [email protected] WITH ANY QUESTIONS OR CONCERNS. |
| | |
| | ADDITIONAL COMMENTS TO THE STANDARDS: |
| | -CALL OUT PIPE SIZE AND MATERIAL. |
| | -SHOW EXISTING VALVES. |
| | -CALL OUT EASEMENTS POINT OF SERVICE CONNECTIONS. |
| | -PROVIDE PROFILE OF EXISTING UTILITIES (WATER, SEWER |
| | AND STORM) WITHIN CITY R/W. |
| | -PROVIDE PROFILE FOR POINT OF SERVICE CONNECTION. |
| | -PROVIDE NOTE THAT THIS IS WITHIN LIFT STATION #21 |
| | SERVICE BOUNDARY. |
| | -PROVIDE CALCULATION FOR SELECTED METER SIZE. |
| | -INCLUDE UTILITY CONFLICT/CROSSING INFO INCLUDING SOFT |
| | DIG/TEST HOLE REPORTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| |