| 2021-08-10 07:13:52 | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPT., 561-494-1098 [email protected] : |
| | |
| | PLEASE CHANGE PROPOSED 3 IN. POLY WATER SERVICE TO 4 |
| | IN. DIP (ON ACACIA FOR 1101 S. FLAGLER DR.). |
| | |
| | MARK HURLEY, CITY OF WPB PUB. UTIL. FIELD CUSTOMER SVC. |
| | SUPV., [email protected]. 561-822-2262: |
| | |
| | -UTILITY PLAN SHOWS REPLACEMENT OF WATER SERVICE FOR |
| | 1101 S. FLAGLER DR. IN ACACIA ROAD. THAT WATER SERVICE |
| | MAY NOT EXIST CURRENTLY, BUT IF IT DOES 3 INCH POLY |
| | SHOULD NOT BE USED. WOULD NEED TO BE DIP. |
| | |
| | -PALM BEACH ATLANTIC COLLEGE HAS A METERED IRRIGATION |
| | WATER SERVICE NEAR THE PROPOSED 4 INCH METER. PRIOR |
| | NOTIFIED APPLICANT TEAM THAT WOULD NEED TO LEAVE IN |
| | TACT OR GET APPROVAL FROM COLLEGE FOR REMOVAL. PLEASE |
| | PROVIDE STATUS/OUTCOME. |
| | |
| | -PLEASE CHECK THE INV OF ALL SAN MH ON CURRIE CRESCENT |
| | TO MAKE SURE GRAVITY WILL GO TO ACACIA ROAD. |
| | |
| | -CIVIL PLANS SHOW GUY WIRE IN SIDEWALK NEAR SOUTH |
| | DRIVEWAY. IS THAT AS INTENDED? |
| | |
| | -LABEL SERVICE PIPE OF 1.5 INCH IRRIGATION METER FOR |
| | ACACIA WITH PIPE SIZE AND MATERIAL TYPE. |
| | |
| | -AREA SOUTHEAST OF PROPOSED FIRE HYDRANT HAS SEVERAL |
| | CROSSINGS WITH WATER PIPE AND UNDERGROUND ELECTRIC. |
| | PLEASE ADD ALL OF THEM TO THE CROSSING TABLE. |
| | |
| | -WRONG STANDARD DETAIL FOR LARGE VAULT METER IS |
| | INCLUDED. PLEASE REPLACE WITH WS-4 AND WS-4.1 REVISION |
| | SEP2019. |
| | |
| | -PIGGING JUMPER ON P-6 DETAIL MUST BE INSTALLED |
| | ABOVE-GROUND. PROJECT SHOULD BE AWARE AND MAKE SURE NO |
| | CONFLICTS WITH PLAN. |
| | |
| | -WHAT IS THE SIZE OF THE CONVERGING TEE IMMEDIATELY |
| | DOWNSTREAM OF THE FIRELINE BACKFLOW ASSEMBLIES? |
| |