Plan Review Notes
Plan Review Notes For Project Z21070014
Project Number Z21070014
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2021-08-10 07:13:52RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPT., 561-494-1098 [email protected] :
  
 PLEASE CHANGE PROPOSED 3 IN. POLY WATER SERVICE TO 4
 IN. DIP (ON ACACIA FOR 1101 S. FLAGLER DR.).
  
 MARK HURLEY, CITY OF WPB PUB. UTIL. FIELD CUSTOMER SVC.
 SUPV., [email protected]. 561-822-2262:
  
 -UTILITY PLAN SHOWS REPLACEMENT OF WATER SERVICE FOR
 1101 S. FLAGLER DR. IN ACACIA ROAD. THAT WATER SERVICE
 MAY NOT EXIST CURRENTLY, BUT IF IT DOES 3 INCH POLY
 SHOULD NOT BE USED. WOULD NEED TO BE DIP.
  
 -PALM BEACH ATLANTIC COLLEGE HAS A METERED IRRIGATION
 WATER SERVICE NEAR THE PROPOSED 4 INCH METER. PRIOR
 NOTIFIED APPLICANT TEAM THAT WOULD NEED TO LEAVE IN
 TACT OR GET APPROVAL FROM COLLEGE FOR REMOVAL. PLEASE
 PROVIDE STATUS/OUTCOME.
  
 -PLEASE CHECK THE INV OF ALL SAN MH ON CURRIE CRESCENT
 TO MAKE SURE GRAVITY WILL GO TO ACACIA ROAD.
  
 -CIVIL PLANS SHOW GUY WIRE IN SIDEWALK NEAR SOUTH
 DRIVEWAY. IS THAT AS INTENDED?
  
 -LABEL SERVICE PIPE OF 1.5 INCH IRRIGATION METER FOR
 ACACIA WITH PIPE SIZE AND MATERIAL TYPE.
  
 -AREA SOUTHEAST OF PROPOSED FIRE HYDRANT HAS SEVERAL
 CROSSINGS WITH WATER PIPE AND UNDERGROUND ELECTRIC.
 PLEASE ADD ALL OF THEM TO THE CROSSING TABLE.
  
 -WRONG STANDARD DETAIL FOR LARGE VAULT METER IS
 INCLUDED. PLEASE REPLACE WITH WS-4 AND WS-4.1 REVISION
 SEP2019.
  
 -PIGGING JUMPER ON P-6 DETAIL MUST BE INSTALLED
 ABOVE-GROUND. PROJECT SHOULD BE AWARE AND MAKE SURE NO
 CONFLICTS WITH PLAN.
  
 -WHAT IS THE SIZE OF THE CONVERGING TEE IMMEDIATELY
 DOWNSTREAM OF THE FIRELINE BACKFLOW ASSEMBLIES?