Plan Review Notes
Plan Review Notes For Project Z21060014
Project Number Z21060014
Review Stop STORM
Sequence Number 3
Notes
Date Text
2022-02-17 12:03:24THE FOLLOWIONG COMMENTS ARE FROM THE REVIEW OF THE
 2/9/2022 SUBMITTAL:
  
 4. [PARTIALLY SATISFIED - PROVIDE VERTICAL DATUM AND
 CONVERSION EQUATION TO SHEET C600 ON ENGINEERING PERMIT
 SUBMITTAL.] LIST THE VERTICAL DATUM ON EVERY SHEET WITH
 ELEVATION INFORMATION. PROVIDE THE CONVERSION EQUATION
 TO NGVD1929 IF DATUM IS DIFFERENT.
  
 5. [SATISFIED] PROVIDE A CROSS SECTION FROM THE EAST
 PARCEL LINE TO THE FACE OF THE BUILDING SHOWING SURFACE
 FEATURES AND TYPICAL PAVEMENT SLOPES.
  
 7. [SATISFIED] CD100 SITE DEMOLITION PLAN
 A. ADD NOTES FOR ALL STORM PIPES AND STRUCTURES WITHIN
 THE DEMOLITION AREA THAT IS TO REMAIN.
 B. ADD VERTICAL DATUM REFERENCE AND CONVERSION EQUATION
 TO NGVD1929.
  
 8. [SATISFIED] CG100 PGD PLAN
 A. PROVIDE CONVERSION EQUATION TO NGVD1929.
 B. PROPOSED GRADING FOR DRIVE-THROUGH LANE TO THE EAST
 OF THE BUILDING SHOWS A LONG FLAT AREA.
 C. PROPOSED GRADING FOR THE TRAVEL LANE EAST OF THE
 ANGLED PARKING SHOWS LONG FLAT AREA.
 D. PROVIDE SPOT GRADES FOR THE FLOW LINE DOWN THE
 CENTER OF THE TRAVEL LANE EAST OF THE ANGLED PARKING.
 E. NO CURBING SHOWN FOR THE GREEN SPACE BETWEEN
 SIDEWALKS ON THE EAST SIDE OF THE BEGINNING OF THE
 TRAVEL LANE FOR THE ANGLED PARKING.
 F. NO CURBING SHOWN AROUND THE GREEN SPACE ON THE WEST
 SIDE OF THE END OF THE DRIVE THROUGH LANE.
  
 9. [ALL BUT 'E' SATISFIED. CAN BE ADDRESSED AT
 ENGINEERING PERMIT SUBMITTAL. PROVIDE AND/OR MODIFY THE
 DETAIL FOR PARKING SPACE STRIPING.] CR300 SIGNAGE AND
 STRIPING PLAN
 A. CROSSWALK STRIPING SHOULD MATCH EXISTING CROSS WALK
 STRIPING IN OTHER AREAS OF THE DEVELOPMENT TO BE
 CONSISTENT.
 B. IS A DO NOT ENTER SIGN NEEDED AT NORTH END OF DRIVE
 THROUGH LANE?
 C. ARE ONE WAY SIGNS NEEDED AT THE NORTH END OF THE
 ANGLED PARKING AREA?
 D. STOP BARS FOR DRIVE THROUGH LANE AND FOR ANGLED
 PARKING AREA.
 E. STRIPING BETWEEN PARKING SPACES (PARALLEL LINES
 CLOSED AT ONE END) SHALL CONFORM TO CITY'S CODE OF
 ORDINANCES (STALL PAINTING DETAIL SECTION 94-485)..
  
 10. [SATISFIED] C600 CONSTRUCTION DETAILS
 A. ANGLED PARKING DETAIL - PARKING SPACE WIDTH IS SHOWN
 AS 9 FT IN THE DETAIL DRAWING AND CALLED OUT AS 8 FT 6
 IN ON SHEET CR300.
 B. SECTION A-A: SHOW SIDEWALK/CURB TO THE RIGHT OF THE
 ANGLED PARKING AS MONOLITHIC SIDEWALK.
 C. DIMENSION THE MONOLITHIC SIDEWALK.
 D. SHOW WHICH WAY THE MONOLITHIC SIDEWALK IS SLOPED.
 E. HOW WILL THE DRIVE-THROUGH TRANSACTIONS OCCUR ACROSS
 THE 5 FEET WIDE MONOLITHIC SIDEWALK NEXT TO THE
 BUILDING?
 F. WILL THE 5 FEET WIDE MONOLITHIC SIDEWALK NEXT TO THE
 BUILDING HAVE A THICKENED EDGE?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  