Plan Review Notes
Plan Review Notes For Project Z21060008
Project Number Z21060008
Review Stop TRAFFIC
Sequence Number 2
Notes
Date Text
2021-09-15 17:50:091) SATISFIED. PROVIDE EXISTING/ORIGINAL 8TH FLOOR PLANS
 FOR SAKE OF COMPARISON
 2) SATISFIED. LABEL AND INDICATE THE PARKING STALLS
 (I.E. ATTENDED, COMPACT, NORMAL)
 3) NOT SATISFIED. THE NUMBER OF ELECTRIC PARKING STALLS
 OR AT THE VERY LEAST THE ORIGINAL PERCENTAGE WITH
 RESPECT TO TOTAL SPACES SHALL BE KEPT; 28 STALLS OR 5%
 OF TOTAL SPACES, RESPECTIVELY
 4) NOT SATISFIED. PROVIDE SAMPLE STANDARD, COMPACT, AND
 ADA PARKING STALL DIMENSIONS
 5) NOT SATISFIED. UNLESS THERE IS A DIRECT ACCESS TO
 OFFICE SPACES AT EACH GARAGE LEVEL, ADA PARKING STALLS
 SHALL BE PROVIDED ON LOWER FLOORS. ACCORDING TO THE
 PARKING TABLE AND TYPICAL GARAGE LEVEL DIAGRAM, IT
 SEEMS POSSIBLE TO RELOCATE FOUR ADA PARKING STALLS FROM
 LEVEL 7 TO LEVEL 4 AND 5 (TWO AT EACH DESTINATION
 LEVEL)
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  