Plan Review Notes
Plan Review Notes For Project Z21050030
Project Number Z21050030
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2021-10-26 07:51:39COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., 561-494-1098 [email protected] :
 1. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 2. FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW
 PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER,
 STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND
 OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL
 AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW.
 DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY,
 PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 3. FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP
 UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY
 LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY.
 4. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE; AND
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION. IF THE ENGINEERING PLANS DO
 NOT INCLUDE AN EROSION CONTROL PLAN, THEN THE
 CONTRACTOR SHOULD SUBMIT ONE PRIOR TO RECEIVING THE
 ENGINEERING PERMIT.
 5. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES
 OF PROPOSED AND EXISTING WATER AND SEWER WITHIN RIGHT
 OF WAY AND SHOW ANY CROSSINGS/CONFLICTS.
 6. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 7. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD
 RIGHT OF WAY.
 8. FOR FORMAL ENGINEERING SUBMITTAL, WHEN TRENCHING IN
 IN CITY MAINTAINED ROADWAY AREAS ADD NOTE TO PROVIDE 50
 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH PER CURRENT CITY OF WPB STANDARD DETAIL
 GC-8.
 9. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
 -IF MAINTENANCE IS NEEDED ON LIFT STATION OR FORCE
 MAIN, WHAT IS THE CONTACT INFORMATION FOR FPL (NAME,
 PHONE, EMAIL)?
 -WATER DEMAND DOCUMENT SAYS 92K GALLONS PEAK DAILY
 IRRIGATION, BUT 30K GALLONS PER WEEK. PLEASE VERIFY
 CALCULATIONS ARE CORRECT AT FORMAL ENGINEERING
 SUBMITTAL.
 -LIFT STATION REPORT SAYS IT WAS BASED ON 1840 FT OF 2
 INCH FM, BUT SOME SIZING WAS INCREASED TO 4 INCH.
 PLEASE VERIFY LIFT STATION WILL STILL FUNCTION
 PROPERLY.
 -PLANS CALLOUT POSSIBLE RECLAIM VALVE IN ROAD. THERE IS
 A LARGE RECLAIM WATER MAIN IN AREA. AT FORMAL
 ENGINEERING SUBMITTAL, PLEASE LOOK AT THE RECLAIM
 ASBUILTS AND SHOW ANY RECLAIM PIPING IN AREA.
 -4 INCH FORCE MAIN CANNOT BE SCH80 PVC. PLEASE UPDATE
 MATERIAL TYPE AT FORMAL ENGINEERING SUBMITTAL.
  
 COMMENTS FROM MICHAEL TECHNOW, PROJECT ENGINEER, WPB
 PUBLIC UTILITIES, 561-494-1047, [email protected] :
 -CALL OUT POINT OF SERVICE ON PLANS AS WELL AS DETAIL A
 .
 -SHOW FM AS ?PRIVATE? UNTIL CONNECTION WITH EXISTING
 CITY SYSTEM.
 -PROVIDE REFERENCE TO THE NEAREST MAJOR STREET/LANDMARK
 IN DETAIL A.
 -SHOW PROPOSED FM IN DETAIL A.
 -ADD NOTE TO ENSURE THAT ANY ROADWAY OR CONSTRUCTION
 RUNOFF IS INCLUDED IN THE MITIGATION PLAN.
 -WHO OWNS THE EXISTING 32? RCP WM? (MATCH LINE C TO D)
 -WHO OWNS THE EXISTING STORM PIPE? (MATCH LINE C TO D)
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  