| 2021-07-06 10:53:19 | FIRE HAS NO OBJECTIONS TO THE PROPOSED; HOEVER, THE | | | FOLLOWING COMMENTS REQUIRE ATTENTIONAND CORRECTION. | | | | | | FIRE'S REVIEW OF THIS SUBMITTED PROJECT DOES NOT | | | CONSTITUTE IT'S FINAL REVIEW. | | | | | | | | | 1. THERE IS AN INDICATION OF A TURNAROUND WITH A 75' | | | DDIMENSION. | | | | | | A TURNAROUND IS REQUIRED; HOWEVER, THE MIN. DIMESION IS | | | 96' WITH A 28' RADIUS. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | 2. THERE ARE INDICATIONS OF GATE ENTRANCE/EGRESS, | | | | | | IT IS RECOMMENDED, NOR REQUIRED, FOR EMERGENCY ACCESS | | | AND SITE SECURITY, THAT IF THE GATE IS ELECTRONIC OPEN, | | | A KNOX KEYSWITCH BE PROVIDED. FOR CHAIN AND LOCK GATE | | | SECURITY THAT A KNOX PADLOCK BE PROVIDED. | | | | | | IN THE EVENT OF AN EMERGENCY INCIDENT, FIRE CREWS WILL | | | NOT BE ABLE TO RELOCK/SECURE A BREECHED ELECTRIC GATE | | | NOR A CUT CHAIN OR LOCK. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OR THAT | | | NIETHER WILL BE PROVIDED. | | | | | | | | | 3. FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS, IF | | | APPLICABLE, AT THE APPROPRIATE TIME AND IN ACCORDANCE | | | WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND | | | STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
| |