Plan Review Notes
Plan Review Notes For Project Z21050030
Project Number Z21050030
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-06 10:53:19FIRE HAS NO OBJECTIONS TO THE PROPOSED; HOEVER, THE
 FOLLOWING COMMENTS REQUIRE ATTENTIONAND CORRECTION.
  
 FIRE'S REVIEW OF THIS SUBMITTED PROJECT DOES NOT
 CONSTITUTE IT'S FINAL REVIEW.
  
  
 1. THERE IS AN INDICATION OF A TURNAROUND WITH A 75'
 DDIMENSION.
  
 A TURNAROUND IS REQUIRED; HOWEVER, THE MIN. DIMESION IS
 96' WITH A 28' RADIUS.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2. THERE ARE INDICATIONS OF GATE ENTRANCE/EGRESS,
  
 IT IS RECOMMENDED, NOR REQUIRED, FOR EMERGENCY ACCESS
 AND SITE SECURITY, THAT IF THE GATE IS ELECTRONIC OPEN,
 A KNOX KEYSWITCH BE PROVIDED. FOR CHAIN AND LOCK GATE
 SECURITY THAT A KNOX PADLOCK BE PROVIDED.
  
 IN THE EVENT OF AN EMERGENCY INCIDENT, FIRE CREWS WILL
 NOT BE ABLE TO RELOCK/SECURE A BREECHED ELECTRIC GATE
 NOR A CUT CHAIN OR LOCK.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT OR THAT
 NIETHER WILL BE PROVIDED.
  
  
 3. FIRE SHALL REVIEW ALL SUBMITTED BUILDING PLANS, IF
 APPLICABLE, AT THE APPROPRIATE TIME AND IN ACCORDANCE
 WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND
 STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  