| 2021-11-10 12:26:36 | ZONING APPROVED WITH THE FOLLOWING CONDITIONS: |
| | |
| | |
| | 1.) THE APPLICANT SHALL PROVIDE A DEED TO THE CITY FOR |
| | THE 959 SQ. FT. RIGHT-OF-WAY DEDICATION ALONG DATURA |
| | STREET PRIOR TO THE ISSUANCE OF A CERTIFICATE OF |
| | COMPLETION. |
| | |
| | |
| | 2.) THE PARKING AREA SHALL BE PAVED WITH A LIGHTLY |
| | REFLECTIVE SURFACE TO REDUCE THE HEAT ISLAND EFFECT ON |
| | THE UNCOVERED SURFACE. |
| | |
| | |
| | 3.) SIGNAGE IS NOT INCLUDED AS PART OF THIS APPROVAL. |
| | ALL SIGNAGE SHALL COMPLY WITH THE SIGNAGE REQUIREMENTS |
| | OF THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS) |
| | AND SHALL BE REVIEWED BY SEPARATE PERMIT. |
| | |
| | |
| | 4.) THE FREESTANDING SIGN LOCATED AT THE DATURA STREET |
| | ENTRANCE SHALL ONLY PROVIDE DIRECTIONAL INFORMATION; |
| | ANY LOGO OR BRANDING INFORMATION IS PROHIBITED ON THIS |
| | SIGN. |
| | |
| | |
| | 5.) THE REMOVABLE FENCE ON THE WEST SIDE OF THE PARKING |
| | AREA SHALL BE OF OPAQUE MATERIAL OR VINYL-COATED CHAIN |
| | LINK. IF VINYL-COATED CHAIN LINK IS USED, ADDITIONAL |
| | SCREENING SHALL BE REQUIRED AND APPROVED BY PLANNING |
| | STAFF. THE REMOVABLE FENCE SHALL BE APPROVED BY |
| | SEPARATE PERMIT. |
| | |
| | |
| | 6.) A LETTER FROM COMCAST, CONFIRMING THAT THE PROJECT |
| | DOES NOT ENCROACH INTO THEIR UTILITY EASEMENT OR |
| | OTHERWISE INTERFERE WITH THE PROVISION OF THEIR SERVICE |
| | SHALL BE PROVIDED TO PLANNING STAFF PRIOR TO ZONING |
| | APPROVAL OF ANY PERMIT FOR THIS PROJECT. |
| | |
| | |
| | 7.) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON |
| | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE |
| | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT |
| | SERVICES DEPARTMENT ? PLANNING DIVISION. |
| | |
| | |
| | 8.) THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE |
| | RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE |
| | RIGHT-OF-WAY LANDSCAPING AND IRRIGATION APPROVED WITH |
| | THIS PETITION. |
| | |
| | |
| | 9.) THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE |
| | RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD |
| | RIGHT-OF-WAY LANDSCAPING AND IRRIGATION APPROVED WITH |
| | THIS PETITION. THIS WILL BE THROUGH A SEPARATE |
| | MAINTENANCE AGREEMENT WITH THE CITY. THE MAINTENANCE |
| | AGREEMENT SHALL BE EXECUTED PRIOR TO THE ISSUANCE OF A |
| | CERTIFICATE OF COMPLETION. |
| | |
| | |
| | 10.) PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR ANY |
| | STRUCTURES, A LANDSCAPE PERMIT SHALL BE SUBMITTED WITH |
| | PLANS REVISED TO MAKE THE FOLLOWING CORRECTIONS: |
| | |
| | A. RELOCATE THE PROPOSED SIMPSON'S STOPPER TREE IN THE |
| | SOUTH BUFFER IN CONFLICT WITH AN EXISTING UTILITY POLE. |
| | |
| | B. PLANT LIST ON SHEET LP-1 IS NOT ACCURATE. REMOVE |
| | FROM SHEET LP-1 AND ONLY INCLUDE ACCURATE PLANT LIST ON |
| | SHEET LP-2. |
| | |
| | C. REMOVE CREEPING FIG ON COLUMNS. IF THE VINES WERE TO |
| | ATTACH TO THE DECORATIVE HISTORIC TILES, THEY COULD |
| | DAMAGE THE SURFACE. |
| | |
| | D. MICRO-MOBILITY STATION WAS MOVED NORTH, PLANTINGS |
| | ARE TO BE EXTENDED ALONG THE BUILDING WHERE A UTILITY |
| | POLE AND TRASH RECEPTACLE BLOCK ACCESS. |
| | |
| | |
| | 11.) PLEASE ADDRESS THE FOLLOWING FOR ENGINEERING |
| | PERMIT: |
| | |
| | A. SHEET C-203 SHOWS THE ELEVATION OF THE FOUR CORNERS |
| | OF THE SIDEWALK CROSSING THE DRIVEWAY TO BE THE SAME. |
| | THERE SHOULD BE A MINIMUM CROSS SLOPE OF 0.5% FOR |
| | DRAINAGE AND MAXIMUM CROSS SLOPE OF 2% FOR ADA. THE |
| | CROSS SLOPE NEEDS TO BE SHOWN ON SECTION A-A ON SHEET |
| | C-205. |
| | |
| | B. THE VALLEY GUTTER WILL NOT BE PERPENDICULAR TO THE |
| | CURBING ON EITHER SIDE OF THE DRIVEWAY. THE SOUTH EDGE |
| | OF THE VALLEY GUTTER SHOULD BE TANGENT TO THE EP |
| | BETWEEN THE NEW MANHOLE (MH 1) AND THE TYPE 'F' C&G. |
| | |
| | C. ADD VERTICAL DATUM AND CONVERSION EQUATION TO SHEET |
| | C-304. |
| | |
| | D. THE TWO EXISTING PIPES BETWEEN THE CURB INLET TO BE |
| | REMOVED AND THE STRUCTURE ON THE SOUTH SIDE OF DATURA |
| | STREET ARE LESS THAN 15 INCHES IN DIAMETER BECAUSE THE |
| | ELECTRICAL DUCT BANK PREVENTED THE INSTALLATION OF |
| | 15-INCH RCP. PROVIDE POTHOLE INFORMATION ON THE DUCK |
| | BANK WHERE THE STORM PIPE WILL BE CROSSING. SHOW THE |
| | CORRECT SIZE PIPES ON SHEET C-100, C-200 AND C-203. |
| | |
| | E. LABEL THE EXISTING AND PROPOSED PIPE SIZES AND |
| | MATERIAL ON SHEET C-203. |
| | |
| | F. THE SCALE BAR APPEARS TO BE MISLABELED ON SEVERAL |
| | ENGINEERING SHEETS. |
| | |
| | G. IS THE CONCRETE COLLAR (PLAN KEYNOTE #70 ON SHEET |
| | C-200) AROUND THE STRUCTURE CB1 NECESSARY? THE |
| | SURROUNDING PAVEMENT IS SHOWN TO BE CONCRETE. IF COLLAR |
| | IS NEEDED, STAFF SUGGESTS THE COLLAR BE A MINIMUM |
| | 6-INCH THICK INSTEAD OF 3-INCHES SHOWN ON THE DETAIL ON |
| | SHEET C-308. |
| | |
| | H. SHOW OUTLINE OF EXFILTRATION TRENCH ON SHEETS C-200 |
| | AND C-203. |
| | |
| | I. IS YARD DRAIN YD1 NEEDED? CAN THE AREA BE GRADED TO |
| | DRAIN TO CB2? |
| | |
| |
Print |