Plan Review Notes
Plan Review Notes For Project Z21050015
Project Number Z21050015
Review Stop STORM
Sequence Number 1
Notes
Date Text
2021-06-10 11:29:08THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PROJECT SITE IS WITHIN A SPECIAL FLOOD HAZARD AREA.
 DRAFT COASTAL FLOOD ZONE MAPS HAVE BEEN ISSUED BY FEMA
 THAT MAY SHOW A HIGHER BASE FLOOD ELEVATION THAN WHAT
 IS SHOWN ON THE CURRENT FLOOD INSURANCE RATE MAPS. TWO
 FEET OF FREEBOARD ABOVE THE BFE WILL BE REQUIRED FOR
 THE FINISHED FLOOR ELEVATION AND ANY
 MECHANICAL/ELECTRICAL EQUIPMENT.
  
 2. LABEL THE VERTICAL DATUM AND CONVERSION EQUATION TO
 NGVD1929 ON ALL CIVIL ENGINEERING SHEETS WITH ELEVATION
 INFORMATION.
  
 3. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA AND CONSIDER SEA LEVEL RISE.
  
 4. MINIMUM 15 INCH DIAMETER RCP PIPE WITHIN THE RIGHT
 OF WAY.
  
 5. CURB RAMP AT CORNER OF CURRIE CRESCENT AND S. OLIVE
 AVE TO MEET CURRENT ADA CRITERIA.
  
 6. UPDATE FDOT STANDARD INDEX REFERENCES TO FDOT
 STANDARD PLAN REFERENCES.
  
 7. PROVIDE CROSS SECTIONS AT ALL DRIVEWAYS FROM THE
 CENTERLINE OF THE ROAD TO 10 FEET WITHIN THE PROPERTY.
 PROVIDE CROSS SLOPE INFORMATION FOR EACH CHANGE IN
 SLOPE. SHOW THE LOCATION OF THE RIGHT OF WAY LINE.
  
 8. PROVIDE TYPICAL CROSS SECTIONS FOR EACH SIDE OF THE
 BUILDING FROM THE ROAD CENTERLINE TO THE FACE OF THE
 BUILDING. SHOW THE LOCATION OF THE PROPERTY LINE.
  
 9. THE ELEVATION OF THE TRENCH GRATES ACROSS THE
 DRIVEWAYS SHOULD NOT BE LOWER THAN THE PERIMETER BERM
 ELEVATION.
  
 10. PRBS SHOULD BE USED IN STRUCTURES CONNECTED TO
 EXFILTRATION TRENCHES AND ON THE OUTFALL PIPE.
  
 11. SHOW SIDEWALK REPLACEMENT WHERE UTILITIES WILL BE
 CONSTRUCTED.
  
 12. IT APPEARS THERE WILL BE PARKING LOCATED BELOW THE
 GROUNDWATER TABLE ELEVATION. DESCRIBE HOW THE
 GROUNDWATER WILL BE PREVENTED FROM ENTERING THE BELOW
 GRADE PARKING AREA.
  
 13. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP BEFORE THE START OF
 CONSTRUCTION.
  
 4. DRAINAGE CALCULATIONS WILL BE REVIEWED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  