Plan Review Notes
Plan Review Notes For Project Z21050011
Project Number Z21050011
Review Stop STORM
Sequence Number 2
Notes
Date Text
2022-03-01 10:37:17THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 2-17-2022 SUBMITTAL. THEY CAN BE ADDRESSED DURING
 ENGINEERING PERMIT SUBMITTAL.
  
 1. SHOW THE 2-FT PARKING OVERHANG LIMITS (DASHED LINE)
 ON THE PAVEMENT MARKING AND SIGNANGE PLAN, THE UTILITY
 PLAN AND THE LANDSCAPE PLAN.
  
 2. SHEET C-06 PAVEMENT MARKLING AND SIGNANGE PLAN
 A. SHOULD THE DIAGONAL LINES FOR THE LOADING AREA SOUTH
 OF THE BUILDING BE TURNED 90 DEGREES?
 B. ANY SIGNAGE OR PAVEMENT MARKINGS TO INDICATE AREA IS
 A LOADING AREA?
 C. SHOULD LOADING AREA PAVEMENT MARKINGS BE EXCLUDED
 FROM THE PEDESTRIAN CROSSWALK?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT