Plan Review Notes
Plan Review Notes For Project Z21050010
Project Number Z21050010
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2021-06-07 08:20:34Z21050010 ? SCUBA CLUB 4708 N FLAGLER ? INITIAL REVIEW
 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER
 ENGINEERING RELATED DOCUMENTS, GO HERE:
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90
 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY:
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, GO TO:
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG ENTIRE PROJECT FRONTAGE.
 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 15. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 16. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT, (561) 494-1098 [email protected]
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 COMMENTS AS FOLLOWS:
 -WILL THE EXISTING DOCK REMAIN, OR WILL IT BE REMOVED?
 -PLEASE SUBMIT DEMOLITION PLAN IF THERE WILL BE
 DEMOLITION.
 -ON THE WATER PLAN, PLEASE SHOW THE LARGE WATER MAIN
 THAT IS NEAR THE LENGTH OF THE SOUTHERN PROPERTY LINE.
 -WILL THERE BE A STRUCTURE WITH WALLS AROUND THE
 DUMPSTER?
 -PLEASE SHOW ALL EXISTING WATER SERVICES, METERS, AND
 BACKFLOW ASSEMBLIES ON THE WATER PLAN AND LABEL WHAT IS
 HAPPENING TO THEM.
 -LABEL THE EXISTING WATER & SEWER MAINS WITH PIPE SIZE
 AND MATERIAL TYPE.
 -WATER PLAN IS MISSING WATER DEMAND CALCULATIONS.
 PLEASE ADD.
 -SHOW AND LABEL ALL UTILITY POLES NEAR THE WEST
 PROPERTY LINE ON THE CIVIL PLANS.
 -SHOW AND LABEL THE NEAREST FIRE HYDRANT TO FDC ON THE
 WATER PLAN.
 -ARE THERE ANY EXISTING OR PROPOSED WELLS ON SITE?
 -WILL A SEPARATE METERED IRRIGATION WATER SERVICE BE
 NEEDED?
 -LABEL OBJECT ON SITE PLAN THAT IS ABOUT 10 FEET SOUTH
 OF THE NORTHWEST CORNER OF PROPERTY.
 -VERIFY TREES ARE ALLOWED TO BE INSTALLED IN FPL
 EASEMENT.
 -THERE APPEARS TO BE A TREE CONFLICT WITH UTILITY POLE
 NEAR SOUTHWEST CORNER OF PROPERTY.
 -DOMESTIC WATER METER IS NOT SHOWN ON WATER PLAN.
 PLEASE SHOW AND LABEL NEAR THE WEST PROPERTY LINE.
 -IF DOMESTIC WATER METER IS 3 INCHES OR LARGER, IT
 NEEDS TO BE INSTALLED ABOVE-GROUND.
 -SOME TREES NEAR SOUTH PROPERTY LINE MAY CONFLICT WITH
 WATER UTILITIES, ESPECIALLY THE WATER MAIN RUNNING WEST
 TO EAST FOR THE NEIGHBORING PROPERTY.
 -TREES NEAR NORTH PROPERTY LINE MAY CREATE MAINTENANCE
 PROBLEM FOR THE PRIVATE FIRELINE PIPING.
 -PROPERTY OWNER WOULD HAVE TO SUBMIT AND RECORD A
 BACKFLOW COVENANT.
 -DOMESTIC BACKFLOW ASSEMBLY NEEDS TO BE LOCATED
 ADJACENT TO THE DOMESTIC WATER METER NEAR THE WESTERN
 PROPERTY LINE.
 -LOCATION OF PRIVATE WATER UTILITY PIPING UNDER
 DUMPSTER AREA MAY CREATE MAINTENANCE CONFLICT FOR
 PROPERTY OWNER.
 -SHOW GATE VALVE FOR DOMESTIC WATER SERVICE IF IT WILL
 BE LARGER THAN 2 INCHES. TRY TO LOCATE IT OUT OF THE
 SIDEWALK.
 -SHOW ALL EXISTING SEWER LATERALS FOR THE PROPERTY AND
 WHAT IS HAPPENING TO THEM.
 -UTILITY WORK IN STREET MAY REQUIRE PAVEMENT
 RESTORATION OF FLAGLER DRIVE.
 -CONSIDER INSTALLING PARALLEL/DUAL BACKFLOW ASSEMBLIES
 FOR THE DOMESTIC WATER SERVICE TO MINIMIZE WATER
 OUTAGES DURING BACKFLOW MAINTENANCE.
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  