| Date |
Text |
| 2021-06-07 08:20:34 | Z21050010 ? SCUBA CLUB 4708 N FLAGLER ? INITIAL REVIEW |
| | 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF |
| | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY |
| | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND |
| | WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW |
| | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER |
| | ENGINEERING RELATED DOCUMENTS, GO HERE: |
| | HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING |
| | 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH, |
| | FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED |
| | SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90 |
| | UTILITIES, ARTICLE I. SEC. 90-7. |
| | POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE |
| | FACILITIES OF THE CITY: |
| | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE |
| | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY |
| | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, |
| | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. |
| | 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, |
| | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR |
| | MORE INFORMATION, GO TO: |
| | HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING |
| | 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY |
| | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC |
| | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF |
| | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE |
| | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL |
| | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT |
| | [email protected] OR 561-494-1040 FOR FURTHER |
| | ASSISTANCE. |
| | 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS |
| | OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, |
| | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND |
| | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, |
| | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE |
| | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING |
| | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, |
| | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL |
| | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER |
| | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE |
| | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN |
| | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. |
| | PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT |
| | MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL |
| | EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT, |
| | INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & |
| | TELECOMMUNICATION FACILITIES LOCATED ON THE |
| | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL |
| | UTILITY CROSSINGS. |
| | 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY |
| | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY |
| | ROW. |
| | 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE |
| | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB |
| | DEVELOPMENT APPLICATION). |
| | 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND |
| | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM |
| | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE |
| | PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. |
| | 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION |
| | (NAVD 88 AND NGVD 29). |
| | 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND |
| | STORMWATER ALONG ENTIRE PROJECT FRONTAGE. |
| | 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND |
| | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED |
| | AREAS. |
| | 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR |
| | PROPOSED SANITARY LATERALS. |
| | 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE |
| | APPLICABLE. |
| | 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED |
| | LOCATION OF WATER METER AND BACKFLOW PREVENTION. |
| | 15. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE |
| | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING |
| | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT |
| | HIM AT 561-494-2262 OR [email protected] |
| | 16. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS |
| | FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS. |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT, (561) 494-1098 [email protected] |
| | |
| | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, |
| | PLEASE CONTACT 561-494-2262 OR [email protected]: |
| | COMMENTS AS FOLLOWS: |
| | -WILL THE EXISTING DOCK REMAIN, OR WILL IT BE REMOVED? |
| | -PLEASE SUBMIT DEMOLITION PLAN IF THERE WILL BE |
| | DEMOLITION. |
| | -ON THE WATER PLAN, PLEASE SHOW THE LARGE WATER MAIN |
| | THAT IS NEAR THE LENGTH OF THE SOUTHERN PROPERTY LINE. |
| | -WILL THERE BE A STRUCTURE WITH WALLS AROUND THE |
| | DUMPSTER? |
| | -PLEASE SHOW ALL EXISTING WATER SERVICES, METERS, AND |
| | BACKFLOW ASSEMBLIES ON THE WATER PLAN AND LABEL WHAT IS |
| | HAPPENING TO THEM. |
| | -LABEL THE EXISTING WATER & SEWER MAINS WITH PIPE SIZE |
| | AND MATERIAL TYPE. |
| | -WATER PLAN IS MISSING WATER DEMAND CALCULATIONS. |
| | PLEASE ADD. |
| | -SHOW AND LABEL ALL UTILITY POLES NEAR THE WEST |
| | PROPERTY LINE ON THE CIVIL PLANS. |
| | -SHOW AND LABEL THE NEAREST FIRE HYDRANT TO FDC ON THE |
| | WATER PLAN. |
| | -ARE THERE ANY EXISTING OR PROPOSED WELLS ON SITE? |
| | -WILL A SEPARATE METERED IRRIGATION WATER SERVICE BE |
| | NEEDED? |
| | -LABEL OBJECT ON SITE PLAN THAT IS ABOUT 10 FEET SOUTH |
| | OF THE NORTHWEST CORNER OF PROPERTY. |
| | -VERIFY TREES ARE ALLOWED TO BE INSTALLED IN FPL |
| | EASEMENT. |
| | -THERE APPEARS TO BE A TREE CONFLICT WITH UTILITY POLE |
| | NEAR SOUTHWEST CORNER OF PROPERTY. |
| | -DOMESTIC WATER METER IS NOT SHOWN ON WATER PLAN. |
| | PLEASE SHOW AND LABEL NEAR THE WEST PROPERTY LINE. |
| | -IF DOMESTIC WATER METER IS 3 INCHES OR LARGER, IT |
| | NEEDS TO BE INSTALLED ABOVE-GROUND. |
| | -SOME TREES NEAR SOUTH PROPERTY LINE MAY CONFLICT WITH |
| | WATER UTILITIES, ESPECIALLY THE WATER MAIN RUNNING WEST |
| | TO EAST FOR THE NEIGHBORING PROPERTY. |
| | -TREES NEAR NORTH PROPERTY LINE MAY CREATE MAINTENANCE |
| | PROBLEM FOR THE PRIVATE FIRELINE PIPING. |
| | -PROPERTY OWNER WOULD HAVE TO SUBMIT AND RECORD A |
| | BACKFLOW COVENANT. |
| | -DOMESTIC BACKFLOW ASSEMBLY NEEDS TO BE LOCATED |
| | ADJACENT TO THE DOMESTIC WATER METER NEAR THE WESTERN |
| | PROPERTY LINE. |
| | -LOCATION OF PRIVATE WATER UTILITY PIPING UNDER |
| | DUMPSTER AREA MAY CREATE MAINTENANCE CONFLICT FOR |
| | PROPERTY OWNER. |
| | -SHOW GATE VALVE FOR DOMESTIC WATER SERVICE IF IT WILL |
| | BE LARGER THAN 2 INCHES. TRY TO LOCATE IT OUT OF THE |
| | SIDEWALK. |
| | -SHOW ALL EXISTING SEWER LATERALS FOR THE PROPERTY AND |
| | WHAT IS HAPPENING TO THEM. |
| | -UTILITY WORK IN STREET MAY REQUIRE PAVEMENT |
| | RESTORATION OF FLAGLER DRIVE. |
| | -CONSIDER INSTALLING PARALLEL/DUAL BACKFLOW ASSEMBLIES |
| | FOR THE DOMESTIC WATER SERVICE TO MINIMIZE WATER |
| | OUTAGES DURING BACKFLOW MAINTENANCE. |
| | |
| | RESPECTFULLY, |
| | |
| | MARK HURLEY |
| | FIELD CUSTOMER SERVICE SUPERVISOR |
| | CITY OF WEST PALM BEACH PUBLIC UTILITIES |
| | 561-822-2262 |
| | |
| |
Print |