2021-09-08 09:41:01THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 6/22/2021 SUBMITTAL PACKAGE:
  
 1. [SATISFIED] SHOW ON THE DEMOLITION PLAN, SHEET C-03,
 THE EXISTING DRAINAGE PIPE CONNECTIONS FOR THE TWO
 CATCH BASINS IN THE NORTHEAST AREA OF THE SITE.
  
 2. [NOT SATISFIED - CAN BE ADDRESSED DURING ENGINEERING
 PERMIT SUBMITTAL] THE PGD PLAN (SHEET C-04) CALLS OUT
 8' X 10' EXFILTRATION TRENCH BUT THE EXFILTRATION
 TRENCH DETAIL ON SHEET C-06 SHOWS 10' X 6.5' TRENCH
 DIMENSIONS.
  
 3. [SATISFIED] THE EXFILTRATION TRENCH DETAIL SHOWS A
 WEIR ELEVATION OF 15.70 FT NAVD.
 A. WHERE IS THIS WEIR LOCATED?
 B. LOWEST FINISHED GRADE IS 16.10. SUGGEST USING
 CRUSHED CONCRETE BASE INSTTEAD OF LIMEROCK BASE TO
 CONTEND WITH POTENTIAL SATURATED BASE CONDITIONS.
 C. THE PROPOSED FINISHED GRADE OF THE LAWN OVER THE
 RAINTANKS IS SHOWN TO BE 16.50' NAVD. SHOULD THE
 FINISHED GRADE BE A MINIMUM OF 1 FOOT ABOVE THE WEIR
 ELEVATION?
  
 4. [SATISFIED] LABEL THE VERTICAL DATUM ON EVERY SHEET
 WITH ELEVATION INFORMATION AND PROVIDE THE CONVERSION
 EQUATION TO NGVD1929. THIS COMMENT APPLIES TO SHEET
 C-03, C-05, C-06, C-07, AND C-11.
  
 5. [SATISFIED] SHOW MINIMUM HORIZONTAL CLEARANCE
 BETWEEN S.S.M.H. #4 AND THE 8" WATER MAIN TO THE NORTH
 AND NORTHWEST OF THE STRUCTURE
  
 6. [SATISFIED] IF THE TRENCH CUT FOR THE PROPOSED 12"
 WATER MAIN IS WITHIN THE NORTHBOUND LANE OF CLEARWATER
 DRIVE, THE FULL WIDTH OF THE NORTHBOUND LAND WILL NEED
 TO BE MILLED AND RE-SURFACED.
  
 7. [SATISFIED] AVOID HAVING VALVE COVERS FALL WITHIN
 THE CURB AND GUTTER.
  
 8. [SATISFIED] USE THE LATEST CITY DETAILS.
  
 9. [SATISFIED] INDICATE IF THE PROPOSED DRAINAGE SYSTEM
 CHANGED WITH THE LATEST SITE PLAN.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION.
  
 4. DRAINAGE CALCULATIONS WILL BE REVIEWED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  