Plan Review Notes
Plan Review Notes For Project Z21040018
Project Number Z21040018
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2021-06-25 07:57:13PASSED WITH PROVISOS:
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 (561) 494-1098, [email protected]
 PLEASE UPDATE STANDARD DETAIL GS-1 AND GS-2. CONTACT
 [email protected] FOR CAD FILES.
 PLEASE LABEL WHAT WILL HAPPEN WITH THE EXISTING
 SANITARY LATERALS COMING OFF THE VCP SANITARY LINE THAT
 IS TO BE REMOVED FROM CLEARWATER DR. (IF ACTIVE
 SERVICES, RECONNECT; IF LARGER THAN 2 IN. REMOVE, ETC).
 ALSO PLEASE SHOW THOSE ADJACENT SERVICE ADDRESSES.
  
 MARK HURLEY, FIELD CUSTOMER SERVICE SUPERVISOR, CITY OF
 WPB PUBLIC UTILITIES 561-822-2262 [email protected]
 -PROPOSED IRRIGATION BACKFLOW ASSEMBLY SHOULD NOT BE
 LOCATED IN UTILITY EASEMENT. PLEASE ADJUST UTILITY
 EASEMENT BOUNDARIES AT FORMAL ENGINEERING SUBMITTAL.
  
  
  Print