2021-05-13 13:27:54COMMENTS TO APRIL 13, 21 SET
 1. PLEASE PROVIDE RENDERINGS TO ILLUSTRATE THE
 TREATMENT OF THE GROUND FLOOR USES AND THE GARAGE
 SCREENING. RENDERINGS SHALL ALSO BE PROVIDED FOR THE
 ENTIRE BUILDING. SOME VIEWS SHALL BE PROVIDED FROM THE
 PEDESTRIAN PERSPECTIVE.
 2. PLEASE REDUCE THE HEIGHT OF THE NORTH GARAGE
 ENTRANCE ON THE FA?ADE. THIS ENTRANCE IS NOT FOR TRUCKS
 OR SERVICE VEHICLES. A 17? CLEARANCE SEEMS EXCESSIVE.
 3. NORTH FA?ADE DOES NOT INDICATE EXTERIOR DOORS FOR
 THE RETAIL SPACE FACING THE POS.
 4. SOME ARCHITECTURAL TREATMENT SHALL BE PROVIDED ON
 THE SOUTH GARAGE ELEVATION AS IT IS VISIBLE FROM THE
 STREET.
 5. THE WEST PARKING GARAGE SHALL BE SCREEN WITH SOME
 ARCHITECTURAL TREATMENT AS IT IS VISIBLE FROM THE
 CIRCULAR DRIVEWAY.
 6. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSS THE
 TWO DRIVEWAYS ON CLEARWATER DRIVE.
 7. IS THE PROJECT COMPLETING THE FULL DESIGN OF THE
 PUBLIC OPEN SPACE AT THIS POINT SO NO FUTURE SUBMITTALS
 ARE NEEDED?
 8. PLEASE INDICATE THE SEATING WALLS WITHIN THE POS.
 9. PLEASE CLEARLY DEPICT THE BOUNDARIES OF THE POS.
 GOING AROUND THE UNDERGROUND STORAGE WILL RESULT ON THE
 POS NOT COMPLYING WITH THE REQUIREMENTS.
 10. 1. HARDSCAPE AND LANDSCAPE ALONG THE POS SHALL BE
 ADJUSTED TO ENSURE THE SPACE CAN BE USED BY THE PUBLIC
 (SUFFICIENT SPACE FOR TABLES FOR A POSSIBLE
 RESTAURANT). ALSO ALONG THE CLEARWATER DRIVE FRONTAGE.
 IT SEEMS THERE IS A VERY NARROW PATH NEXT TO THE FA?ADE
 AND THEN PLANTING.
 11. PLEASE INDICATE HOW THE BALCONIES IN LEVEL 7 ARE
 GOING TO BE SEPARATED BETWEEN UNITS.
 12. PARKING LEVEL ABOVE THE 5TH STORY SHALL BE SET BACK
 A MINIMUM OF 27? FROM THE BACK OF CURB.
 13. PLEASE CONFIRM THE PROPOSED LOCATION OF THE
 REQUIRED BIKE RACKS ALONG THE BUILDING FRONTAGE MEETS
 THE MINIMUM SPACING REQUIRED (DISTANCE BETWEEN RACKS).
 IT MAY BE IN CONFLICT WITH THE MICROMOBILITY STATION.
 14. PLEASE PROVIDE INFORMATION TO CONFIRM THE PROJECT
 COMPLIES WITH THE MAXIMUM BUILDING FOOTPRINT AT EACH
 FLOOR, SPECIALLY THE MIN 55% BUILDING FOOTPRINT FOR
 FLOOR 6TH.
 15. LOADING ARE ACCESS FROM CLEARWATER DRIVE SHALL
 INCLUDE AN OPAQUE ROLLING GATE.
 16. IN SITE PLAN SHEET A 0.10 PLEASE INCLUDE THE
 SIDEWALK AND PROPOSED STREET TREES.
 17. PLEASE PROVIDE PHOTOMETRICS FOR THE GROUND FLOOR
 EXTERIOR TO CONFIRM COMPLIANCE WITH SEC 94-113 B.
 18. INSIDE THE PARKING GARAGE PLEASE INDICATE THE
 LOCATION OF RETAIL/COMMERCIAL PARKING, GUEST PARKING
 AND SPACES RESERVED FOR THE CAR SHARED PARKING.
 19. TOTAL NUMBER OF PARKING PROVIDED SEEMS TO EXCEED
 THE MAXIMUM NUMBER OF PARKING SPACES ALLOWED FOR THE
 PROJECT. 604 MAXIMUM ALLOWED VS 628 PROVIDED.
 20. ALL MECHANICAL EQUIPMENT ON THE ROOF SHALL BE
 SCREENED.
 21. MICRO MOBILITY STATION INDICATED ON THE NW CORNER
 OF BUILDING NEEDS TO BE RELOCATED TO THE STREET
 FRONTAGE.
 22. STAFF RECOMMENDS SOME PLANTING BED TO BE INSTALLED
 ON THE NORTH SIDE OF THE NORTH DRIVEWAY TO REDUCE THE
 NEGATIVE IMPACT OF THE VEHICULAR ENTRANCE. ALLOW A
 MINIMUM 8 FEET WIDE PEDESTRIAN ACCESS.
 23. PLEASE CONFIRM THE NEW BUILDING IS GOING TO BE
 SERVED WITH THE EXISTING UTILITY ABOVE GROUND VALVES
 CURRENTLY EXISTING EAST OF THE OPEN SPACE. IF ANY
 ADDITIONAL VALVES NEEDED, PLEASE INDICATE ITS LOCATION.
 FDC SHALL BE WALL MOUNTED WHEN POSSIBLE.
  
 PLEASE RESUBMIT TWO PAPER COPIES OF THE COMPLETE SET OF
 DRAWINGS AND SUPPORTING DOCUMENTATION AND A CD WITH
 ELECTRONIC COPIES. PLEASE INCLUDE A RESPONSE LETTER
 ADDRESSING ALL COMMENTS. PROJECTS IS REQUIRED TO GO TO
 DAC FOR SPECIAL REVIEW. ALL THE PPRC COMMENTS SHALL BE
 SATISFIED BEFORE THE PROJECT CAN BE SCHEDULED FOR DAC.
 SOME ITEMS MAY BE INCLUDED AS CONDITIONS OF APPROVAL.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  