2022-02-02 16:31:45THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 12-10-2021:
  
 1. ON THE CIVIL DRAWINGS, INDICATE BY HATCHING AND
 CALLOUTS, PROPOSED CONCRETE CONSTRUCTION.
  
 2. AT THE SOUTH END OF THE MIDDLE PARKING LOT, THE
 SLOPE OF THE SIDEWALK BETWEEN HANDICAP ACCESS AISLE AND
 SIDEWALK ALONG RAILROAD AVE MAY NOT MEET ADA CRITERIA.
 CHECK THE SLOPE OF THE SIDEWALK FROM 9TH STREET TO THE
 NORTH PARKING LOT ALSO.
  
 3. PROVIDE SPOT GRADES FOR THE ALLEY NORTH OF 9TH
 STREET. WILL THERE BE A BERM ALONG THE NORTH PROPERTY
 LINE?
  
 4. CONSIDER SLOPING THE WEST EDGES OF THE PARKING LOTS
 SO THAT THE WHEEL STOPS DO NOT TRAP WATER.
  
 5. CHECK THE NORTH-SOUTH DIMENSIONS OF ALL THE PARKING
 AREAS. FOR EXAMPLE, THE SOUTH HALF OF THE PARKING LOT
 BETWEEN THE ALLEY AND 9TH STREET MEASURES 50.5 FT
 BETWEEN THE CURBS OF THE LANDSCAPE ISLANDS. IF THE SIX
 PARKING SPACES ARE EACH 8.5 FEET WIDE, THEN THE
 DISTANCE SHOULD BE 51 FEET. THE NORTH HALF OF THE
 PARKING LOT SOUTH OF THE ALLEY MEASURES 42 FEET BUT FOR
 FIVE 8.5 FEET WIDE PARKING SPACES, THE DISTANCE SHOULD
 BE 42.5 FEET.
  
 6. HOW WAS THE BERM ELEVATIONS DETERMINED FOR THE RIGHT
 SIDE OF SECTIONS A, B, AND C?
  
 7. CIVIL PLAN PARKING LAYOUT DOES NOT MATCH THE LAYHOUT
 SHOWN ON SHEET SP1 OF 1. FOR EXAMPLE, SHEET SP1 OF 1
 SHOWS ON EITHER SIDE OF THE 4.5 WIDE STRIP TO THE WEST
 OF THE CENTER PARKING SPACES IN THE NORTH PARKING LOT
 AND THE CIVIL PLANS DOES NOT SHOW THE CURBING. EXAMPLE
 2, IN THE SAME PARKING LOT, SP1 OF 1 DOES NOT SHOW
 CURBING ALONG THE EDGE OF PAVEMENT BETWEEN THE HANDICAP
 PARKING SPACES AND THE DRIVEWAY ENTRANCE (AND ALONG THE
 OTHER OUTER EDGES OF THE PARKING AREAS OF THE LOT) AND
 THE CIVIL PLANS DO.
  
 8. PROVIDE DETAIL SHOWING HOW THE PARALLEL HANDICAP
 PARKING SPACES ARE TO BE STRIPED.
  
 9. SUGGEST ADDING CENTERLINE STRIPING AT STOP BARS
 SINCE THE ENTRANCES ARE ONLY 20 FEET WIDE.
  
 10. WILL EASTBOUND TURNS ONTO THE ALLEY BE ALLOWED FROM
 THE PARKING LOTS ON EITHER SIDE OF THE ALLEY?
  
 11. REPLACE DETAIL SHOWING HAY BALE PROTECTION OF
 INLETS WITH ALTERNATIVE METHOD/MATERIALS.
  
 12. THE SITE DEMOLITION PLAN SHOWS THE CLOSING OF THE
 ALLEY.
  
 13. THE NORTH EDGE OF THE NORTH PARKING LOT IS CUTOFF
 IN THE PLAN VIEW.
  
 14. LOCATE THE CONSTRUCTION ACCESS OUTSIDE OF THE RIGHT
 OF WAY.
  
 15. DRAINAGE STRUCTURES AT THE EAST END OF THE STREETS
 MAY REQUIRE INLET PROTECTION.
  
 16. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 17. SUGGEST LOCATING LIGHT POLES OPPOSITE THE STRIPING
 BETWEEN PARKING SPACES INSTEAD OF OPPOSITE THE WHEEL
 STOPS TO REDUCE THE LIKELIHOOD OF THE LIGHT POLE
 GETTING HIT WHEN ADJACENT TO THE 2-FOOT OVERHANG AREA.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  