Notes
Date Text
2021-12-22 09:43:50NO COMMENTS FROM RICK ROSSANO, PROJECT COORDINATOR,
 ENG. SERVICES DEPT., 561-494-1098 [email protected] :
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPER., WPB PUBLIC UTILITIES, 561-494-2262 OR
 [email protected]:
 -AUTOTURN EXHIBIT DOES NOT SHOW ALL FOUR PARKING LOTS.
 PLEASE ADD THE MISSING ONE.
  
 -SITE PLAN SHOWS ALLEY BETWEEN 8TH AND 9TH ST. AS
 ONE-WAY GOING EAST. IS THAT FOR THE ENTIRE ALLEY? ALSO
 THE ONE-WAY DIRECTION IS NOT CLEAR ON THE CIVIL PLANS.
 ARE ANY ADDITIONAL SIGNS OR PAVEMENT MARKINGS NEEDED?
  
 -SITE PLAN SHOWS SIGNAGE IN MIDDLE OF 9TH ST.
  
 -CIVIL PLANS DO NOT SHOW GAS MAIN AND GAS MAIN VALVE
 THAT RUN IN ALLEY BETWEEN 8TH AND 9TH ST. PLEASE SHOW
 AND LABEL TO ENSURE NO CONFLICTS.
  
 -THERE MAY BE A GAS MAIN IN SOUTH PARKWAY OF 8TH ST.
 PLEASE VERIFY AND SHOW ON CIVIL PLANS IF THERE.
  
 -TWO TRANSFORMERS ARE PROPOSED AT EDGE OF STREETS. DO
 THEY NEED ANY PROTECTION FROM VEHICLE COLLISION?
  
 -ENSURE PROPOSED BIKE RACK AND STREET LIGHT LOCATIONS
 MEET CLEARANCE DISTANCE REQUIREMENTS FROM FIRE HYDRANTS
 AS SHOWN IN STANDARD DETAIL P-8.
  
 -C1.1 AND C1.3 SHOWS WHAT APPEARS TO BE A LIGHT POLE IN
 DRIVEWAY AT 9TH ST. IT WOULD ALSO BE IN CONFLICT WITH
 PROPOSED SEWER UTILITY.
  
 -DO ANY OF THE ELECTRIC UTILITIES, SUCH AS
 TRANSFORMERS, NEED UTILITY EASEMENTS?
  
 -IF PROPOSED SEWER MAIN THAT IS RUNNING THROUGH PARKING
 LOT IS CITY OWNED AND MAINTAINED, THEN THERE SHOULD BE
 A UTILITY EASEMENT SHOWN AND LABELED FOR IT ON C1.1.
  
 -CIVIL PLANS DO NOT SHOW SEVERAL EXISTING WATER
 SERVICES, METERS, BACKFLOWS, AND BOXES FOR THE PARKING
 LOT PROPERTIES. THOSE NEED TO BE ACCOUNTED FOR AND
 PLANNED FURTHER. APPLICANT/PROJECT MAY HAVE TO REMOVE
 OR RELOCATE THEM AND WILL HAVE TO RESOLVE ANY ACCOUNTS
 WITH CITY WPB UTILITY BILLING.
  
 -C1.1 DOES NOT SHOW EXISTING WATER MAIN RUNNING DOWN
 ALLEY BETWEEN 8TH ST. AND 9TH ST. PLEASE SHOW AND LABEL
 TO ENSURE NO CONFLICTS.
  
 -UTILITY EASEMENTS MAY BE REQUIRED FOR METERED WATER
 SERVICES IF ON PRIVATE PROPERTY.
  
 -E.2 SHOWS ELECTRIC PB IN A TREE ON 9TH ST.
  
 -AFTER LOOKING AT PLANS, NOT SURE IF THERE IS
 IRRIGATION FOR THE SOUTHERN THREE PARKING LOTS AND HOW
 IT WILL WORK. THERE MAY BE ADDITIONAL REQUIREMENTS OR
 CONFLICTS DEPENDING ON PROPOSED DESIGN.
  
  