2021-08-10 10:30:39COMMENTS PER RICK ROSSANO, PROJ. COORD. WPB ENG.
 SERVICES, [email protected], 561-494-1098:
 PLEASE SHOW DRY UTILITIES ON RAILROAD AVE.
 PLEASE SHOW IRRIGATION DEMANDS ON ENGINEERING SHEET.
 ON DEMO SHEET, PLEASE ADD NOTE TO PROTECT CATCH BASINS
 ON RAILROAD AVE. ALONG PROJECT FRONTAGE.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 COMMENTS AS FOLLOWS FOR Z21040012:
 -TRANSFORMER, IRRIGATION METERS, AND BACKFLOW
 ASSEMBLIES APPEARS TO BE PROPOSED IN SAME LOCATION.
 DISTANCE WATER METER BOXES AND BACKFLOW ASSEMBLIES AT
 LEAST 3 FEET AWAY FROM TRANSFORMER. VERIFY NONE OF THEM
 WILL HAVE CONFLICT WITH TREES EITHER.
 -SHOW PROPOSED IRRIGATION METERS AND BACKFLOW
 ASSEMBLIES ON CIVIL/ENGINEERING PLAN.
 -SHOW PROPOSED SEWER MAIN RUNNING THROUGH PARKING LOT
 ON CIVIL/ENGINEERING PLAN. VERIFY IT WILL NOT HAVE
 CONFLICT WITH TREES.
 -ADD NOTE TO IRRIGATION PLAN THAT BACKFLOW ASSEMBLIES
 NEED TO BE RP TYPE, LEAD-FREE, AND MEET REQUIREMENTS OF
 WATER SERVICE STANDARD DETAIL WS-6 REVISION SEP2019.
  