| 2022-05-19 16:26:36 | INFORMAL SITE PLAN REVIEW 21-05 - APRIL 20, 2022 |
| | RESUBMITTAL |
| | PUBLIX @ SOUTHDALE |
| | 804 SOUTHERN BOULEVARD |
| | |
| | - CONTACT ERIC SCHNEIDER @ (561) 822-1446, |
| | [email protected] |
| | |
| | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN |
| | WRITTEN FORMAT. |
| | |
| | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE |
| | (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT |
| | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE |
| | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS |
| | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL |
| | COMMENTS. |
| | |
| | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT |
| | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS |
| | FROM THE DATE OF THESE COMMENTS (BY JUNE 20, 2022), THE |
| | PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE |
| | CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL |
| | REQUIRE A NEW DEVELOPMENT APPLICATION. |
| | |
| | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) |
| | ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF |
| | PREVIOUSLY ISSUED COMMENTS CONTINUE TO NOT BE |
| | SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED |
| | A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL |
| | APPLICATION FEE ($200). |
| | |
| | 1) UPDATED COMMENT: THANK YOU FOR PROVIDING THE GENERAL |
| | PARKING DIMENSION DETAIL TABLE; HOWEVER, THE STALL |
| | DEPTH THAT YOU HAVE LISTED FOR 45 ST AT 17.75 IS NOT |
| | ACTUALLY THE STALL DEPTH IN ACCORDANCE WITH THE MEASURE |
| | REQUIRED BY STALL PAINTING DETAIL "C", AND AS LISTED |
| | DOES NOT MEET THE MINIMUM CODE REQUIRED STALL DEPTH. |
| | WHEN SCALING THE PLAN, THE "C" DEPTH IS CLOSER TO 21 |
| | FEET IN DEPTH (YOUR CAD MEASURE WILL BE ACCURATE). YOU |
| | DO NOT NEED TO UPDATE THE SITE PLAN DIMENSIONS, BUT YOU |
| | WILL NEED TO UPDATE THE TABLE TO SHOW THE CORRECT STALL |
| | DEPTH DIMENSION. |
| | |
| | 2) UPDATED COMMENT: NOT ALL THE SCREEN WALL LOCATIONS |
| | ARE SHOWN ON THE LANDSCAPE PLANS - THE PUBLIX COMPACTOR |
| | SCREEN WALL IS MISSING. |
| | |
| | 3) STAFF WILL BE ISSUING A REASONABLE ACCOMMODATION FOR |
| | THE WEST SIDE RAMP AND HANDRAIL. PLEASE PROVIDE REVISED |
| | ELEVATION DRAWINGS THAT SHOW THE RAMP AND HANDRAIL, TO |
| | INCLUDE THE HEIGHT OF EACH AT THE HIGHEST POINTS. THE |
| | REVISED ELEVATION DRAWINGS SHALL INCLUDE ALL UPDATED |
| | PLAN ELEMENTS BUT DOES NOT NEED TO BE IN COLOR. |
| | |
| | 4) CONDITION (DRAFT): THE MICRO-MOBILITY STATION AREA |
| | MUST BE PROVIDED WITH BASIC ELECTRIFICATION READINESS |
| | CONSISTING OF AN ELECTRICAL PULL BOX (240V CIRCUIT) AND |
| | 2-INCH SCHEDULE 40 PVC ELECTRIC CONDUIT TO THE POWER |
| | SOURCE. THE ELECTRICAL READINESS MUST BE APPROVED BY |
| | THE CITY'S TRAFFIC ENGINEER AND INSTALLED PRIOR TO THE |
| | CERTIFICATE OF OCCUPANCY FOR THE NEW PUBLIX. |
| | |
| | |
| |