Plan Review Notes
Plan Review Notes For Project Z21040002
Project Number Z21040002
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2021-08-05 07:21:02COMMENT PER RICK ROSSANO, PROJECT COORDINATOR, ENG.
 SERVICES DEPT., DIRECT: (561) 494-1098 [email protected]
  
 PLEASE SHOW PARAMETERS OF UTILITY EASEMENTS FOR
 PROPOSED UTILITY WATER METERS IN BLOW UP 1 ON PAGE
 C-501.
  
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
 -THERE IS CROSS WALK AT NORTH SIDE OF BUILDING WITH
 MARKINGS THAT RUN INTO ISLAND CURB. PLEASE CORRECT.
  
 -THE ACCESSIBILITY PLAN DOES NOT SHOW ROUTE FROM ROW
 SIDEWALK TO BANK. IS THERE ONE?
  
 -ADD A SMALL UTILITY EASEMENT ALL THE WAY AROUND THE
 PROPOSED FIRE HYDRANT WITH ITS PIPING.
  
 -ONE OF THE WATER SERVICES NEAR THE DUMPSTER DOES NOT
 HAVE PLUMBING PIPE SHOWN. IS IT FOR IRRIGATION?
  
 -WILL THE IRRIGATION WATER SERVICE AT NORTH SIDE OF THE
 PROPERTY IRRIGATE THE SOUTH SIDE OF PROPERTY?
  
 -FOR FORMAL ENGINEERING SUBMITTAL: ADD ADDITIONAL GATE
 VALVES IN THE GRASS AFTER THE SIDEWALK FOR THE
 FIRELINES NEAR THE DUMPSTER AND LABEL THEM POINT OF
 SERVICE; LABEL ALL PROPOSED WATER SERVICE PIPE WITH
 PIPE SIZE AND MATERIAL TYPE.
  
 -IS THE SEWER LATERAL FOR THE WESTERN BUILDING SHOWN ON
 THE UTILITY PLAN?
  
 -VERIFY THE EXISTING WATER SERVICE SHOWN IN THE AREA OF
 BLOW UP 1 IS BEING REMOVED, AND ONE OF THE PROPOSED NEW
 METERED WATER SERVICES WILL CONTINUE PROVIDING WATER
 SERVICE AFTER PROJECT IS COMPLETED.
  
 -THE SEWER LATERALS FOR THE EAST BUILDING AND BANK ARE
 NOT SHOWN ON UTILITY PLAN. IF THEY ARE CONNECTED TO THE
 EXISTING 8 INCH CLAY SEWER PIPE AT THE REAR OF THE
 STORES, WILL THE EXISTING AND PROPOSED SEWER SYSTEMS
 FUNCTION PROPERLY?
  
 -THERE APPEAR TO BE BOLLARDS AROUND THE PROPOSED FIRE
 HYDRANT. CHECK TO SEE IF THEY COMPLY WITH STANDARD
 DETAIL P-8.
  
 -1.5 INCH METERS REQUIRE 2 INCH SERVICE PIPE BETWEEN
 THE METER AND WATER MAIN.
  
 -PAVEMENT RESTORATION BOUNDARIES ON NOTTINGHAM LOOK
 SMALLER THAN REQUIRED. CHECK DIMENSIONS NEEDED ON THE
 TRENCHING OR PAVEMENT RESTORATION STANDARD DETAILS AND
 ADJUST.
  
 -IS THERE AN FDC FOR THE EASTERN PROPOSED 8 INCH DCDA?
 IF NOT, IS ONE NEEDED?
  
 -ARE ANY OF THE PROPOSED RETAIL SHOPS PLANNING TO BE
 RESTAURANTS?
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  