Plan Review Notes
Plan Review Notes For Project Z21030022
Project Number Z21030022
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2021-05-09 08:41:311. PLEASE SHOW CALCULATIONS ON PRELIMINARY PLANS OF
 EXISTING AND PROPOSED DEMANDS FOR WATER & SEWER
 (AVERAGE, MAXIMUM AND PEAK. CALCULATIONS SHALL BE PER
 FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 2. PLEASE PROVIDE CCTV VIDEO OF EXISTING SANITARY AND
 STORM SEWER ALONG ENTIRE PROJECT FRONTAGE (CCTV IS A
 CONDITION OF SITE PLAN APPROVAL).
 3. PLEASE RESPOND TO ALL COMMENTS IN WRITING.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES, 561-822-2262
 [email protected]
  
 PLEASE RESPOND TO THE FOLLOW COMMENTS IN WRITING:
  
 -ABOVE-GROUND METER MAY HAVE LARGER FOOTPRINT THAN
 SHOWN ON THE CIVIL PLANS.
  
 -4 INCH PVC SEWER NOT RUNNING THROUGH GREASE
 INTERCEPTOR HAS GREASE LABEL.
  
 -FENCES APPEARS TO BE RUNNING OVER WATER SERVICES NEAR
 GEORGIA PROPERTY LINE. ENSURE THAT FENCES ARE
 ELIMINATED OR REROUTED SO METERS CAN BE ACCESSED AT ROW
 WITHOUT GOING THROUGH MAIN ENTRANCE, AND SO WATER
 SERVICES CAN BE MAINTAINED.
  
 -MH #5 HAS TWO INV LISTED. DOES IT NEED ONE FOR EACH
 PIPE?
  
 -IF WATER IS NEEDED FOR LIFT STATION MAINTENANCE, WHERE
 WILL IT COME FROM? WILL THE WATER SOURCE HAVE ADEQUATE
 BACKFLOW PROTECTION?
  
 -FOR FORMAL ENGINEERING SUBMITTAL HAVE SEPARATE CIVIL
 PLAN SHEETS WITH WATER SERVICE STANDARD DETAILS THAT
 ARE USED. ENSURE THEY ARE THE NEWEST REVISION AND
 NUMBERS MATCH THE LABELS.
  
 -NEAR THE CLUBHOUSE THE FDC PIPES CROSS THE OTHER
 FIRELINE PIPING. CONSIDER NOT HAVING THEM CROSS.
  
 -AT NORTH SIDE OF OFFICE BUILDING THERE IS SOMETHING
 THAT LOOKS LIKE A BACKFLOW ASSEMBLY NEAR A DOOR. IS
 ACCESSIBILITY FINE?
  
 -METER SIZE WAS LEFT OFF THE ABOVE-GROUND METER. PLEASE
 ADD AT FORMAL ENGINEERING SUBMITTAL.
  
 -PLEASE LOCATE THE PROPOSED 3 INCH METER SLIGHTLY WEST
 IN A SIMILAR FASHION TO THE ABOVE GROUND METER.
  
 -3 INCH METER SHOULD BE ABOVE GROUND DESIGN.
  
 -3 INCH METER MAY HAVE LARGER FOOTPRINT THAN
 REPRESENTED ON THE CIVIL PLANS.
  
 -POLY CANNOT BE USED UPSTREAM OF 3 INCH METER. IT
 SHOULD ALSO HAVE 4 INCH TAP AND PIPING PER STANDARD
 DETAILS.
  
 -PLEASE LABEL PROPERTY LINES ON WATER PLANS.
  
 -ONE OF THE METERS AT MADDOCK AND PARKER INTERSECTION
 IS WPB UTILITY?S AND MAY NOT BE USED. THE OTHER DOES
 NOT CURRENTLY HAVE METER INSTALLED OR AN ACTIVE USAGE
 ACCOUNT. APPLICANT WOULD HAVE TO SETUP ACCOUNT AND MEET
 REQUIREMENTS OF CITY WPB UTILITY BILLING.
  
 -PLANS DO NOT SHOW WHERE WATER COMES FROM FOR THE
 MAINTENANCE BUILDING OR WHERE THE SEWAGE GOES. NEEDS TO
 BE DETERMINED AND FURTHER REQUIREMENTS MAY BE NEEDED
 BASED ON FINDINGS.
  
 -GUY WIRE ANCHOR SHOWS SLIGHTLY ENCROACHING ON CART
 PATH ON LANDSCAPE PLAN NEAR MADDOCK AND PARKER.
  
 -ENSURE PROTECTIVE NETTING POSTS DO NOT CONFLICT WITH
 SEWER PIPE OR DRAINAGE/STORMWATER PIPE.
  
 -SHOW WHERE 60 INCH DRAINAGE GOES ON LANDSCAPE PLANS AT
 THE WEST SIDE OF MARY BRANDON PARK.
  
 -LANDSCAPE PLAN SHOWS TRANSFORMER AND EMERGENCY
 GENERATOR NEAR CLUBHOUSE GREASE TRAP. PLEASE SHOW
 TRANSFORMER AND GENERATOR ON SEWER PLAN ALONG WITH ANY
 CONCRETE PADS THEY HAVE.
  
 -PLEASE ADD SEPARATE WATER PLAN SHEET SHOWING WATER
 UTILITIES SOUTH OF THE INTERSECTION OF GREGORY AND
 GEORGIA AVE.
  
 -SITE PLAN SHOWS FPL UTILITY EASEMENT NEAR THE SOUTHERN
 WATER METERS. PLEASE SHOW THAT EASEMENT ON WATER PLAN
 AND VERIFY ANY GUY WIRES DO NOT CONFLICT WITH WATER
 UTILITIES.
  
 -ELEVATION NOT SHOWN NEAR 8? DCDA?S. PLEASE ENSURE
 THOSE AREAS ARE NOT LOW SPOTS OR DEPRESSIONS.
  
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 MOBILE: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  