Plan Review Notes
Plan Review Notes For Project Z21030020
Project Number Z21030020
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2021-07-06 18:39:19-UTILITY PLAN SAYS HOTEL HAS A RESTAURANT. IS THERE A
 GREASE TRAP/INTERCEPTOR PROPOSED?
  
 -LOOKS TO BE SEVERAL TREE CONFLICTS WITH PRIVATE
 UTILITIES: FIRE HYDRANT, SOUTHERN FDC, LIFT STATION
 WATER LINE. ALSO POSSIBLE TREE CONFLICT WITH STRUCTURE
 THAT LOOKS LIKE SIGN MONUMENT NEAR THE WATER METER.
  
 -PLEASE ADD ABOVE-GROUND METER WATER SERVICE STANDARD
 DETAIL REV. SEP2019 TO CIVIL PLANS AND UPDATE
 REFERENCED NUMBERS ON THE BLOWUP DETAIL. WS-3 SHOULD BE
 THE METER AND FIRELINE DCDA SHOULD BE WS-5.
  
 -ADD ?PRIVATE? TO LABEL OF THE FIRE HYDRANT.
  
 -DEMO PLAN SAID FIRE HYDRANTS ARE BEING REMOVED. WILL
 THE PIPES FEEDING THE FIRE HYDRANTS ALSO BE REMOVED?
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  