2021-03-05 15:51:501.BUILDING FOOTPRINT AT FLOOR 7 AND 8 NEEDS TO BE
 ADJUSTED TO REFLECT THE POOL AND AND BALLROOM DECK
 EXTENSION. PLEASE CONFIRM THE MAXIMUM BUILDING
 FOOTPRINT DOES NOT EXCEED THE MAXIMUM ALLOWED PER
 FLOOR.
 2.SHEET A0.07 NEEDS TO BE ADJUSTED TO REFLECT THE
 CHANGES IN FAR INDICATED IN SHEET A0.06. A0.06 SHOWS
 REVISED GBA AT 806,310 VS PREVIOUS 824,645SF. WAS THE
 TOTAL GBA REDUCED?
 3.SHEET A1.07 SHOWS A ROOM LABEL STAFF HK AND LAUNDRY
 AS OFFICE SPACE. IF THIS SPACE IS TO BE COUNTED FOR
 CLASS A OFFICE SPACE IT CAN NOT BE USED BY THE HOTEL.
 4.ON THE SOUTH ELEVATION, THE GREEN WALL USED TO EXTEND
 FROM THE 6TH TO THE 7TH FLOOR. NOW THE ELEVATION SHOWS
 A WALL WITH NO GREEN SCREEN. PLEASE EXPLAIN.
 5.IS THE PROPOSED EAST FA?ADE CORRECT? THE GREEN WALL
 EXTENDS ABOVE THE 7TH FLOOR WHERE THE POOL IS? THE EAST
 ELEVATION DOES NOT SHOW THE GREY BAND AT FLOOR 6TH
 SHOWN ON THE SOUTH ELEVATION. HOW DOES THIS WORK?
 PLEASE SUBMIT ONE FULL SET WITH REVISIONS AND AN CD
 WITH ELECTRONIC COPY OF ALL DOCUMENTS.