| Date |
Text |
| 2021-09-08 07:09:55 | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, |
| | PLEASE CONTACT 561-494-2262 OR [email protected]: |
| | |
| | DIDN?T SEE PRIOR COMMENTS ON RESPONSE LETTER: |
| | -PARKING FEATURES ON NORTH SIDE OF BISCAYNE DR BETWEEN |
| | FIRE HYDRANT AND GATE DO NOT MATCH ON CIVIL PLANS AND |
| | SITE PLANS. PLEASE UPDATE ALL PLANS SO THEY MATCH. |
| | -DID NOT SEE UPDATED LANDSCAPING PLAN IN SUBMITTAL |
| | PACKAGE. IS THE PLAN FROM 5/28/21 STILL ACCURATE? |
| | -BACKFLOW ASSEMBLIES MAY NOT BE UNDERGROUNDED. |
| | NEW COMMENTS: |
| | -AT FORMAL ENGINEERING SUBMITTAL, REVISE UTILITY |
| | EASEMENT BOUNDARIES TO INCLUDE EXISTING FIRE HYDRANT, |
| | EXISTING WATER METER FOR SCHOOL, AND EXISTING 4 INCH CA |
| | WM |
| | |
| | |
| | THE FOLLOWING COMMENTS ARE FROM MICHAEL TECHNOW, |
| | PROJECT ENG., WPB PUBLIC UTIL. 561-494-1047, |
| | [email protected] : |
| | |
| | - FIRE HYDRANT VALVE NEEDS TO BE CLOSER. |
| | - PLEASE PROVIDE PROFILE FOR PROPOSED AND EXISTING |
| | UTILITIES. |
| | - PLEASE SHOW DRY UTILITIES. |
| | - THE 4? WM CANNOT BE SHUT DOWN, PLEASE SPECIFY HOW THE |
| | CONNECTION WILL BE MADE WHILE MAINTAINING SERVICE. |
| | - REPLACE CAS PIPE IN ROW. |
| | - MAINTAIN HORIZONTAL SEPARATION FROM 20? WM (NOTE |
| | HORIZONTAL CLEARANCE ON PLANS). |
| | - ADD NOTE TO SUPPORT EXISTING 20? WM, RESTRAIN AS |
| | REQUIRE, EXERCISE CAUTION. |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT |
| | DIRECT: (561) 494-1098 [email protected] |
| | |
| | |
| | |
| |
Print |