Plan Review Notes
Plan Review Notes For Project Z21010029
Project Number Z21010029
Review Stop SURVEY
Sequence Number 2
Notes
Date Text
2021-03-29 10:25:301. SURVEY STILL NOT SIGNED.
 2. NEED SURVEY OF ALLEY.
 3. SHOW EXISTING SANITARY ON SP-1.
 4. OLD UE'S WILL NEED TO BE ABANDONED. PROVIDE COPIES
 FOR OWNERSHIP.
 5. ENG. PLANS SHOW EXISTING STORM MANHOLE ON TOP OF
 EXISTING WATER MAIN AT WEST END OF BISCAYNE?
 6. EXISTING DRAINAGE FROM DIXIE (FDOT) DRAINS INTO THE
 EASTERN 2 CATCH BASINS THEN OUT INTO THE DIXIE DRAINAGE
 SYSTEM. PRIOR TO APPROVAL WE WILL NEED TO KNOW FROM
 FDOT HOW TO HANDLE. CONSULTANT TO CONTACT FDOT TO
 RESOLVE.
  
 PREVIOUS COMMENTS FOR REPLAT AND EASEMENT RESERVATION
 STILL PERTAIN.