| Plan Review Notes For Project Z21010029 |
| Project Number |
Z21010029 |
|
| Review Stop |
ENG - PPRC |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-26 13:52:44 | COMMENTS FROM RICK ROSSANO, PROJ. COORD., ENG. | | | SERVICES, [email protected], 561-494-1098: | | | | | | PLEASE PROVIDE CCTV OF EXISTING SANITARY AND STORMWATER | | | INFRASTRUCTURE IN BISCAYNE DR. ALONG PROJECT FRONTAGE | | | (REQUIREMENT OF SITE PLAN APPROVAL). | | | | | | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD | | | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, | | | PLEASE CONTACT 561-494-2262 OR [email protected]: | | | | | | -PLEASE VERIFY LOCATION OF STM MANHOLE ON CLAREMORE IS | | | CORRECT. | | | | | | -CANNOT FIND THE PROPOSED BOUNDARIES OF UTILITY | | | EASEMENTS ON BISCAYNE DRAWN AND LABELED ON WATER PLAN. | | | PLEASE UPDATE PLAN BEFORE NEXT RESUBMITTAL. | | | | | | -FOR FORMAL ENGINEERING SUBMITTAL: LABEL ALL WATER MAIN | | | GATE VALVES ON BISCAYNE DR., VERIFY IF THE 20 INCH | | | WATER MAIN IS CAST IRON OR ASBESTOS, SHOW AND LABEL ALL | | | WATER MAIN VALVES FOR 20 INCH WATER MAIN, VERIFY IF ANY | | | EXISTING SEWER INFRASTRUCTURE AROUND BUILDING TO BE | | | DEMOLISHED NEAR CLAREMORE. | | | | | | -SITE PLAN SHOWS THAT ROLLING GATE HAS A KEYPAD IN | | | CONJUNCTION WITH REQUEST TO BRIAN CARROLL, BUT PRIOR | | | COMMENT RESPONSE SAID KNOX BOX. PLEASE CONFIRM PUBLIC | | | UTILITIES WILL HAVE A KEYPAD GATE CODE FOR 24/7 | | | MAINTENANCE ACCESS INSTEAD OF KNOX BOX. | | | |
| |