Plan Review Notes
Plan Review Notes For Project Z21010029
Project Number Z21010029
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2021-02-05 13:42:481. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER
 ENGINEERING RELATED DOCUMENTS, OPEN A BROWSER IN CHROME
 AND GO TO: WWW.WPB.ORG/ENGDOCS . TO LOGIN, UNDER
 ?EMAIL? ENTER [email protected] ; UNDER ?PASSWORD? ENTER
 SIMPLE321#
 THERE ARE 4 PAGES OF AVAILABLE ENGINEERING DOCUMENTS
 FOR YOUR USE.
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90
 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY:
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, OPEN A BROWSER IN CHROME AND GO TO:
 WWW.WPB.ORG/ENGDOCS .TO LOGIN, UNDER ?EMAIL? ENTER
 [email protected] ; UNDER ?PASSWORD? ENTER SIMPLE321#
 CROSS-CONNECTION CONTROL MANUAL IS ON PAGE 4.
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER ALONG BISCAYNE DR.
 10. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 11. CLEARLY SHOW PROPOSED UTILITY CONNECTIONS FOR WATER
 AND SEWER TO PROPOSED NEW BUILDING.
 12. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 13. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION.
 14. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 15. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -NEED UTILITY EASEMENTS GRANTED FOR ALL CITY UTILITY
 INFRASTRUCTURE ON PRIVATE PROPERTY INCLUDING THE WATER
 AND SEWER MAINS. PLEASE SHOW AND LABEL ON CIVIL
 ENGINEERING PLANS.
  
 -SHOW AND LABEL THE EXISTING METERED WATER SERVICES FOR
 THE SCHOOL WHICH ARE LOCATED ON THE NORTH SIDE OF
 BISCAYNE DR.
  
 -SITE PLAN SHOWS WHAT APPEARS TO BE AN TELEPHONE POLE
 IN THE MIDDLE OF THE LOADING DRIVEWAY ENTRANCE.
  
 -SHOW AND LABEL ALL EXISTING FIRE HYDRANTS ON OR AROUND
 THE PROPERTY. THERE IS AT LEAST ONE NEAR THE
 INTERSECTION OF BISCAYNE AND DIXIE WHICH IS NOT
 LABELED.
  
 -VERIFY PIPE MATERIAL TYPE OF THE 4INCH WATER MAIN.
  
 -LABEL 4INCH G.V. NUMBER 3 ? FIRELINE POINT OF SERVICE.
  
 -LABEL THE FIRE SERVICE PIPE WITH SIZE AND MATERIAL
 TYPE.
  
 -WILL ANOTHER METERED IRRIGATION WATER SERVICE BE
 NEEDED?
  
 -TENNIS FACILITY BUILDING APPEARS TO BE LOCATED ON TOP
 OF AND CLOSE TO THE 20 INCH WATER MAIN WHICH IS A
 MAINTENANCE AND UTILITY EASEMENT CONFLICT. PLEASE
 RESOLVE CONFLICT.
  
 -THERE APPEARS TO BE SOME WATER MAIN PIPING THAT IS
 ENTERING THE NORTHWEST CORNER OF THE 454 FLAMINGO
 PROPERTY. PLEASE SHOW CLEARLY ON WATER PLAN WHERE IT
 TERMINATES AND GRANT UTILITY EASEMENT IF INSIDE
 PROPERTY LINE.
  
 -SHOW AND LABEL ALL EXISTING UTILITY EASEMENTS ON WATER
 PLAN. FOR EXAMPLE, SITE PLAN SHOWS A 2FOOT UTILITY
 EASEMENT RUNNING THROUGH THE SCHOOL WHICH IS NOT
 DEPICTED ON THE WATER PLAN.
  
 -SHOW AND LABEL THE EXISTING METERED WATER SERVICES FOR
 453 CLAREMORE AND 454 FLAMINGO AND DETAIL WHAT IS
 HAPPENING TO THE THEM.
  
 -COULD NOT FIND DEMOLITION PLAN. PLEASE SUBMIT DEMO
 PLAN IF THERE WILL BE DEMOLITION.
  
 -WATER PLAN SHOWS A WATER MAIN RUNNING NORTH-SOUTH
 THROUGH THE SCHOOL BUILDING AND PROPERTY. PLEASE VERIFY
 AND UPDATE PLAN AS NEEDED.
  
 -WATER SERVICE STANDARD DETAILS ARE OLD REVISION.
 PLEASE UPDATE TO NEWEST REVISION.
  
 -PROPOSED ROLLING GATE ON BISCAYNE WOULD CREATE ACCESS
 PROBLEM FOR UTILITY PERSONNEL DOING EMERGENCY
 MAINTENANCE OR WATER METER READING. PLEASE ELIMINATE
 ROLLING GATE.
  
 -PROPOSED MONUMENT NEAR DIXIE IS IN CLOSE PROXIMITY TO
 EXISTING WATER MAIN WHICH COULD CREATE MAINTENANCE
 CONFLICT. PLEASE INFORM HOW HEAVY MONUMENT WOULD BE.
 ALSO LABEL DISTANCE BETWEEN WATER MAIN AND PROPOSED
 MONUMENT AND SEE IF DISTANCE CAN BE INCREASED.
  
 -WHAT IS HAPPENING TO EXISTING DRIVEWAY APPROACH ON
 CLAREMORE ADJACENT TO TENNIS FACILITY?
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  
  
  