2021-02-11 11:23:06THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. COMMENTS WITHHELD PENDING SUBMITTAL OF ENGINEERING
 PLANS SHOWING CURRENT SITE PLAN.
  
 2. INCLUDE CONCEPTUAL DEMOLITION PLAN WITH THE NEXT
 SUBMITTAL.
  
 3. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 4. PROVIDE CROSS SECTIONS FROM CENTERLINE OF STREET TO
 BUILDING FACE FOR ALL SIDES OF THE BUILDINGS,
 PREFERABLY AT LOCATIONS WHERE ON-STREET PARKING IS
 BEING ADDED. LABEL RIGHT OF WAY LINES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE COPY OF MODIFIED SFWMD ERP PERMIT BEFORE
 START OF CONSTRUCTION.
  
 4. PROVIDE A COPY OF THE DRAINAGE CALCULATIONS WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  