| 2021-04-22 11:27:02 | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD |
| | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, |
| | PLEASE CONTACT 561-494-2262 OR [email protected]: |
| | |
| | -PLEASE ADD NOTE OR LABEL TO UTILITY PLAN INCORPORATING |
| | RESPONSE TO PRIOR COMMENT ABOUT BUILDING STRUCTURES |
| | ENCROACHING ON EXISTING UTILITY EASEMENTS. |
| | |
| | -PLEASE ADD MORE DESCRIPTION TO LABEL OF 6 INCH METER |
| | ON INSET A OF UTILITY PLAN DESCRIBING WHAT THE WATER |
| | METER IS FEEDING, SIMILAR TO THE 3 INCH METER. |
| | |
| | -SHOW AND LABEL DRAINAGE FOR FIREROOM ON INSET A OF |
| | UTILITY PLAN. |
| | |
| | -THE BYPASSES FOR THE LARGE WATER METERS MAY NOT BE |
| | SHOWN TO SCALE ON UTILITY PLAN AND MAY EXTEND CLOSER TO |
| | THE BOLLARDS. |
| | |
| | -FURTHER FEEDBACK/DIRECTION ON THE WATER MAIN WORK MAY |
| | BE PROVIDED AT FORMAL ENGINEERING SUBMITTAL. |
| | |
| | -PAVEMENT RESTORATION BOUNDARIES APPEAR SMALLER THAN |
| | REQUIRED BY STANDARDS. PLEASE SHOW THE ADDITIONAL |
| | PAVEMENT RESTORATION BOUNDARIES FOR THE SEWER WORK IN |
| | THE STREETS AND MAKE SURE BOUNDARIES COMPLY WITH |
| | STANDARDS. |
| | |
| | -WPB GIS AND ASBUILT SHOW EXISTING 8 INCH SEWER LATERAL |
| | AT EAST SIDE OF PROPERTY NEAR PROPOSED 6 INCH C900. |
| | PLEASE CONFIRM IF STILL THERE AND SHOW AND LABEL AS |
| | NEEDED. |
| | |
| | -TRAFFIC ARROWS ARE MISSING FOR SOUTHERN DRIVEWAY ON |
| | UTILITY PLAN. PLEASE ADD. |
| | |
| | -CONFIRM THAT THE PROPOSED 8 INCH SEWER LATERALS MAY |
| | HAVE 6 INCH CLEANOUTS. |
| | |
| | -VERIFY FIRE HYDRANTS HAVE THE NECESSARY CLEARANCE |
| | DISTANCES REQUIRED BY STANDARD DETAIL P-8. |
| | |
| | -FIRE HYDRANTS APPEAR TO BE HALF IN PLANTERS AND HALF |
| | IN SIDEWALKS. CAN PLANTERS BE EXTENDED SLIGHTLY AT |
| | THOSE AREAS SO THAT THE FIRE HYDRANTS ARE COMPLETELY IN |
| | THE PLANTER? |
| | |
| | -THE PROXIMITY OF SOME OF THE WATER UTILITIES TO TREES |
| | IS STILL CONCERNING. PLEASE ENSURE BOTH IRRIGATION |
| | METERS AND FIRE HYDRANTS HAVE ADEQUATE CLEARANCE |
| | DISTANCE. IF ROOT BARRIERS ARE BEING UTILIZED, PLEASE |
| | SHOW THOSE ON LANDSCAPE PLAN. |
| | |
| | -PARKS EXISTING METERED IRRIGATION SERVICE CURRENTLY |
| | HAS 2 INCH METER. RELOCATED WATER SERVICE ONLY SHOWS 1 |
| | INCH METER. PLEASE CONFIRM THAT WPB PARKS APPROVED THE |
| | SIZE REDUCTION. ALSO ENSURE THAT A BACKFLOW CAGE IS |
| | INSTALLED IF REQUIRED BY PARKS. |
| | |
| | -PLEASE SHOW AND DESCRIBE HOW WPB UTILITY WORKERS WILL |
| | ACCESS THE WATER METERS THAT ARE ON THE FIRELINE |
| | BACKFLOW ASSEMBLIES IN THE FIREROOM. |
| | |
| | -PROPERTY OWNER WILL BE REQUIRED TO SUBMIT AND RECORD |
| | BACKFLOW COVENANT. CONTACT [email protected] FOR TEMPLATE |
| | AND DIRECTION. |
| | |
| | -CHECK SOUTHERN-MOST FLAG POLE ON WEST SIDE OF PROPERTY |
| | TO SEE IF IT CONFLICTS WITH DRAINAGE UTILITY. |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT, (561) 494-1098 [email protected] |
| | |
| |