Plan Review Notes
Plan Review Notes For Project Z20120015
Project Number Z20120015
Review Stop STORM
Sequence Number 1
Notes
Date Text
2021-02-11 11:42:16THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. DRAINAGE CALCULATIONS WERE FOR 3200 ELECTRONICS WAY.
 STORMWATERMANAGEMENT CALCULATIONS ARE FOR THIS PROJECT.
 THESE WILL BE REVIEWED DURING ENGINEERING PERMIT
 REVIEW.
  
 2. IF ASPHALT IS BEING REMOVED AROUND THE DETENTION
 AREA, CONSIDER REDUCING THE PARKING SPACE DEPTHS BY TWO
 FEET AND HAVE AN ADDITIONAL 2 FEET OF LANDSCAPE
 OVERHANG.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 4. DRAINAGE CALCULATIONS WILL BE REVIEWED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT