Plan Review Notes
Plan Review Notes For Project Z20120014
Project Number Z20120014
Review Stop ENG - PPRC
Sequence Number 1
Notes
Date Text
2020-12-17 20:28:10-ELECTRICAL STRUCTURE APPEARS TO HAVE BEEN BUILT OVER
 WATER SERVICE LINE IN UTILITY EASEMENT NEAR THE WATER
 METERS CREATING A MAINTENANCE CONFLICT WHERE PIPING
 COULD NOT BE REPAIRED IN THE EVENT OF A LEAK. CONFLICT
 NEEDS TO BE RESOLVED BEFORE PROJECT APPROVAL, OR REMEDY
 SATISFACTORY TO WPB PUBLIC UTILITIES INCLUDED IN
 PROJECT SCOPE/DESCRIPTION.
  
 -BUSHES APPEAR TO BE VERY CLOSE TO, OR ON TOP OF,
 FIRELINE BACKFLOW ASSEMBLY. PLEASE ENSURE 16IN
 CLEARANCE BETWEEN BACKFLOW ASSEMBLIES AND BUSHES FOR
 MAINTENANCE AND TESTING.
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  
 PLEASE PROVIDE VERTICAL DATUM CONVERSION NOTE ON ALL
 RELEVANT CIVIL SHEETS.
 PLEASE PROVIDE SWPPP SHEET WITH BMP DETAILS - DUST
 CONTROL, INLET PROTECTION ETC.
 PLEASE ADD RELEVANT CITY OF WPB STANDARD DETAILS FOR
 PAVING, PAVEMENT MARKING DETAILS ETC.
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  