2021-08-30 14:01:41REGARDING THE PROPOSED CONCRETE BENCHES, UTILITY
 COMMENTS NOTE THAT SEVERAL PROPOSED BENCHES CONFLICT
 WITH EXISTING FORCE MAIN AND SEWER LINES. THE BENCHES
 WOULD NEED TO BE MOVED BACK TO THE GREATEST EXTENT
 POSSIBLE (MIN. 2 FEET) FROM THESE UTILITY LINES TO
 PROVIDE ACCESS AND CLEARANCE NECESSARY FOR MAINTENANCE.
 PLEASE SPECIFY IF THE BENCHES PROPOSED CAN BE MOVED BY
 HEAVY MACHINERY, IF NOT, MAY NEED TO PROVIDE
 ALTERNATIVE LIGHTER MATERIAL OR BENCH DESIGNS.