Plan Review Notes
Plan Review Notes For Project Z20110019
Project Number Z20110019
Review Stop STORM
Sequence Number 2
Notes
Date Text
2021-03-11 06:17:56THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 2/12/2021 SUBMITTAL:
 1. SHOW EXISTING UTILITY POLES ON SHEET C-3.
  
 2. MOVE THE STORMWATER MANHOLE AT THE EAST END OF THE
 EXFILTRATION TRENCH (OR ENTIRE EXFILTRATION SYSTEM) TO
 THE WEST AWAY FROM THE UTILITY POLE.
  
 3. HIGH LIGHT ON THE CIVIL PLANS (THROUGH COLOR) WHERE
 THE RAILROAD TRACK WILL BE LOCATED (WILL REMAIN). THE
 SITE PLAN SHOWS SEVERAL PLANTING AREAS OVER THE TRACKS.
  
 5. LABEL THE VERTICAL DATUM ON ALL SHEETS THAT CONTAIN
 ELEVATION INFORMATION (SHEETS C-2, C-3, C-5, C-7)
  
 6. PROVIDE THE WIDTH OF THE EXFILTRATION TRENCH ON THE
 EXFILTRATION TRENCH DETAIL ON SHEET C-7.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120 (O)
 561-351-0510 (M)
  