Plan Review Notes
Plan Review Notes For Project Z20110019
Project Number Z20110019
Review Stop ENG - PPRC
Sequence Number 2
Notes
Date Text
2021-02-16 08:37:24THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -GHOST TRAIN CART STILL APPEARS TO BE A MAINTENANCE
 CONFLICT FOR THE WATER UTILITIES UNDERNEATH IT AS NOTED
 IN PRIOR COMMENT. PLEASE RESOLVE THIS CONFLICT, AND
 PROVIDE EXPLANATION OF HOW RESOLVING.
  
 -ARE THE 20INCH DIP WM AND 14INCH FM WHICH ARE LABELED
 ABANDONED ON SHEET C-8, CURRENTLY ABANDONED OR PROPOSED
 TO BE ABANDONED?
  
 -PLEASE LABEL DISTANCE BETWEEN THE LIGHT POLES NEAR THE
 30INCH FM AND ENSURE THAT THE CLEARANCE DISTANCE IS AT
 LEAST 5FT.
  
 -LIGHT POLE NEAR EX. MH-4 APPEARS TO BE TOO CLOSE.
 PLEASE LABEL CLEARANCE DISTANCE AND ENSURE IT IS AT
 LEAST 5FT.
  
 -IN-GROUND LIGHTING APPEARS TO BE A MAINTENANCE
 CONFLICT WITH THE 20INCH VCP SS, 18INCH SS, 30INCH FM,
 AND 1INCH PE WM. PLEASE RESOLVE THOSE CONFLICTS, AND
 PROVIDE EXPLANATION OF HOW RESOLVING.
  
 -PLEASE VERIFY THERE IS A GATE VALVE NEAR THE SOUTHWEST
 CORNER OF GHOST TRAIN CART, AND LABEL WHAT TYPE ON
 SHEET C-8. IF VALVE IS STILL FUNCTIONAL, THEN IT WOULD
 NOT OPERABLE WITH A GHOST TRAIN CART OVER IT ? PLEASE
 RESOLVE THAT CONFLICT ALSO.
  
  