| 2021-02-16 08:37:24 | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD | | | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, | | | PLEASE CONTACT 561-494-2262 OR [email protected]: | | | | | | -GHOST TRAIN CART STILL APPEARS TO BE A MAINTENANCE | | | CONFLICT FOR THE WATER UTILITIES UNDERNEATH IT AS NOTED | | | IN PRIOR COMMENT. PLEASE RESOLVE THIS CONFLICT, AND | | | PROVIDE EXPLANATION OF HOW RESOLVING. | | | | | | -ARE THE 20INCH DIP WM AND 14INCH FM WHICH ARE LABELED | | | ABANDONED ON SHEET C-8, CURRENTLY ABANDONED OR PROPOSED | | | TO BE ABANDONED? | | | | | | -PLEASE LABEL DISTANCE BETWEEN THE LIGHT POLES NEAR THE | | | 30INCH FM AND ENSURE THAT THE CLEARANCE DISTANCE IS AT | | | LEAST 5FT. | | | | | | -LIGHT POLE NEAR EX. MH-4 APPEARS TO BE TOO CLOSE. | | | PLEASE LABEL CLEARANCE DISTANCE AND ENSURE IT IS AT | | | LEAST 5FT. | | | | | | -IN-GROUND LIGHTING APPEARS TO BE A MAINTENANCE | | | CONFLICT WITH THE 20INCH VCP SS, 18INCH SS, 30INCH FM, | | | AND 1INCH PE WM. PLEASE RESOLVE THOSE CONFLICTS, AND | | | PROVIDE EXPLANATION OF HOW RESOLVING. | | | | | | -PLEASE VERIFY THERE IS A GATE VALVE NEAR THE SOUTHWEST | | | CORNER OF GHOST TRAIN CART, AND LABEL WHAT TYPE ON | | | SHEET C-8. IF VALVE IS STILL FUNCTIONAL, THEN IT WOULD | | | NOT OPERABLE WITH A GHOST TRAIN CART OVER IT ? PLEASE | | | RESOLVE THAT CONFLICT ALSO. | | | | | | |
| |