2021-07-19 14:57:22THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 6/16/2021 RESUBMITTAL. THEY CAN BE ADDRESSED FOR
 THEENGINEERING PERMIT APPLICATION.
  
 1. REVISE WATER AND SANITARY SEWER NOTE NO. 5 ON SHEET
 C0.2 TO READ MIN. 36" COVER FROM FINISHED GRADE.
  
 2. REMOVE "32.00' ASPHALT" FROM SECTION B-B (DETAIL 12)
 ON SHEET C4.2. THE PGD PLAN SHOWS PAVERS.
  
 3. PROVIDE ADDITIONAL EXISTING AND PROPOSED SPOT GRADES
 FOR 7TH STREET (CENTERLINE, EDGE OF PAVEMENT)
 DEMONSTRATING THE ROADWAY WILL DRAIN TOWARD THE CURB
 AND GUTTER AND TO THE EXISTINGDRAINAGE STRUCTURE.
 REVISE SECTION C-C TO SHOW THE EXISTING PAVEMENT WILL
 DRAIN TOWARD THE VALLY GUTTER.
  