Plan Review Notes
Plan Review Notes For Project Z20100014
Project Number Z20100014
Review Stop ENG - PPRC
Sequence Number 4
Notes
Date Text
2021-04-09 15:15:24PASSED WITH PROVISOS:
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -FOR FORMAL ENGINEERING SUBMITTAL, ADD SEPARATE PAGE TO
 CIVIL PLANS WITH THE CITY OF WEST PALM BEACH WATER
 SERVICE STANDARD DETAILS THAT WILL BE UTILIZED AND MAKE
 SURE THEY ARE THE NEWEST REVISION. ALSO VERIFY THE GATE
 VALVE SIZE THAT IS BEING UTILIZED BETWEEN THE CROSS AND
 REDUCER ? IT SAYS 6INCH, BUT SEEMS LIKE IT WOULD NEED
 TO BE 8INCH. LASTLY, LABEL THE WATER SERVICE PIPING ON
 INSET A FOR THE 1.5? METERS WITH PIPE SIZE AND MATERIAL
 TYPE.
  
 NEW COMMENT:
  
 -FOR FORMAL ENGINEERING SUBMITTAL, PLEASE LABEL THE 10
 FOOT UTILITY EASEMENTS FOR THE ELECTRIC TRANSFORMERS AS
 EXISTING OR PROPOSED.
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  