2020-12-31 07:07:19PLEASE PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER
 FROM MANHOLE TO MANHOLE ? PLEASE NOTE THAT PROVISION OF
 CCTV IS A REQUIREMENT OF SITE PLAN APPROVAL.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -COMMENT RESPONSE LETTER ITEMS 24-28 DO NOT APPEAR TO
 HAVE THE CORRECT RESPONSES MATCHED UP.
  
 -?20. UTILITY BILLING SYSTEM IS SHOWING SITE AS HAVING
 A 6? FIRELINE THAT IS BEING PAID FOR EACH MONTH. PLEASE
 LABEL ON CIVIL PLAN AND PUT WHAT IS HAPPENING TO IT.
 RESPONSE: THERE IS NO KNOWN EXISTING FIRE LINE ONSITE
 FOR THIS PROPERTY. THE ONLY POSSIBLE FIRE LINE NEAR THE
 SITE IS THE EXISTING FIRE HYDRANT WITHIN THE EXISTING
 UTILITY EASEMENT JUST OUTSIDE OF THE RIGHT-OF-WAY.?
  
 HAD A UTILITY LOCATE SPECIALIST CHECK THE SITE AND THEY
 ARE SEEING UTILITY PIPE CROSSING THE ROAD THAT IS DRAWN
 ON C-1 BUT NOT LABELED. IT IS SHOWN AS 6INCH WATER
 SERVICE ON HISTORIC ASBUILT. THAT APPEARS TO BE THE
 EXISTING FIRELINE THAT IS GETTING CHARGED AND PAID FOR
 EACH MONTH. PROJECT NEEDS TO FIND A WAY TO MAKE USE OF
 IT OR GO THROUGH PROCESS TO ELIMINATE IT.
  
  
 NEW COMMENTS:
  
 -DO NOT PLACE GATE VALVES IN SIDEWALKS.
  
 -PLEASE PLACE GATE VALVE SO THE FIRELINE BACKFLOW
 ASSEMBLY CAN BE INDEPENDENTLY SHUT OFF WITHOUT SHUTTING
 OFF THE DOMESTIC WATER SERVICES. THAT VALVE SHOULD BE
 IN THE EASTERN PART OF UTILITY EASEMENT. ADD LABELING -
 FIRELINE POINT OF SERVICE.
  
 -RECOMMEND 8 BY 6 REDUCER FOR WATER SERVICES BE PLACED
 DOWNSTREAM OF THE DOMESTIC WATER SERVICE CROSS SO THAT
 FIRELINE FLOW IS NOT DIMINISHED.
  
 -THERE WERE SOME TREES ON FAR EAST SIDE OF PROPERTY
 SHOWN ON PLANS THAT WERE IN CLOSE PROXIMITY TO THE
 WATER MAINS. IF THE TREES ARE PROPOSED AND NOT
 EXISTING, THEN PLEASE LOCATE THEM FURTHER AWAY AND ADD
 ROOT BARRIERS.
  
 -FOR FORMAL ENGINEERING SUBMITTAL: PLEASE DRAW AND
 LABEL EXISTING GATE VALVES ON WATER MAINS, LABEL PIPE
 MATERIAL TYPE AND SIZE OF THE DOMESTIC WATER SERVICE
 LINES, AND ADD ADDRESS TO THE CIVIL PLANS.
  
  
  