| 2020-10-15 14:58:17 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL |
| | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION |
| | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE |
| | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT |
| | APPLICATION PROCESSES. |
| | |
| | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE |
| | PLAN APPROVAL: |
| | |
| | 1. PROVIDE THE CONVERSION EQUATION BETWEEN VERTICAL |
| | DATUMS NAVD1988 (BASIS OF SURVEY) AND NGVD1929 (CWPB |
| | OFFICIAL DATUM) ON THE SURVEY. |
| | |
| | 2. THE PROPOSED 4' BLACK METAL PICKET FENCE CONNECTION |
| | TO THE WEST SIDE OF THE BUILDING IS SHOWN FURTHER NORTH |
| | ON THE SITE PLAN (FENCE MEETS AT THE CORNER OF THE |
| | BUILDING) THAN ON THE LANDSCAPE PLANS AND HARDSCAPE |
| | PLANS (FENCE MEETS THE BUILDING MIDWAY BETWEEN THE |
| | CORNERS OF THE BUILDING). |
| | |
| | 3. PERVIOUS PAVERS ARE PROPOSED FOR THE PATIO TO THE NW |
| | OF THE LASSITER BUILDING. PROVIDE MAINTENANCE |
| | RECOMMENDATIONS TO PRESERVE OR RE-ESTABLISH THE |
| | INFILTRATION CAPACITY OF THE PAVERS AND IDENTIFY WHO |
| | WILL BE RESPONSIBLE FOR THIS MAINTENANCE. |
| | |
| | |
| | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO |
| | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. |
| | |
| | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY |
| | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. |
| | |
| | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED |
| | WITH THE ENGINEERING PERMIT APPLICATION. |
| | |
| | TRACY WARD, PE |
| | SENIOR STORMWATER ENGINEER |
| | ENGINEERING SERVICES DEPARTMENT |
| | 561-494-1120 |
| | [email protected] |
| | |
| |