| Plan Review Notes For Project Z20080008 |
| Project Number |
Z20080008 |
|
| Review Stop |
ENG - PPRC |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-03-08 14:39:53 | COMMENTS PER MARK HURLEY, CUSTOMER SERVICE FIELD SUPV., | | | WPB PUBLIC UTILITIES, 561-822-2262, [email protected] : | | | | | | -WATER PLAN SHOWS A LARGE OVAL GROUND DEPRESSION NEAR | | | THE SOUTHEAST CORNER OF THE PROPOSED BUILDING NEAR THE | | | WATER METERS AND BACKFLOW ASSEMBLIES. PLEASE VERIFY IF | | | AREA WILL REMAIN LIKE THAT, OR IF GROUND ELEVATION WILL | | | INCREASE CLOSER TO THAT OF SURROUNDING AREA. (IF NOT, | | | CHANGES TO BACKFLOW ASSEMBLIES AND DOMESTIC METER | | | SERVICE, OR GROUND GRADE MAY BE NEEDED.) | | | -THERE ARE DUPLICATE WATER SERVICE STANDARD DETAILS FOR | | | THE ABOVE-GROUND METER SERVICE AND SMALL BACKFLOW | | | ASSEMBLY. PLEASE REMOVE APR 2018 AND NOV 2018 | | | RESPECTIVELY. | | | -FOR FORMAL ENGINEERING SUBMITTAL, MAKE SURE IRRIGATION | | | METER BOX IS DISTANCED AT LEAST THREE FEET FROM | | | ADJACENT LARGE POLE. SHOW/CALLOUT DISTANCE OR ADD NOTE | | | ON LABEL FOR IRRIGATION METER. (IF IRRIGATION BOX IS | | | ADJUSTED SOUTH, THEN FIRELINE MAY NEED ADJUSTMENT SOUTH | | | AS WELL.) | | | -PLEASE VERIFY THERE IS NO GATE OR FENCE BETWEEN | | | SIDEWALK AND PROPOSED METERS/BACKFLOWS. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT, 561-494-1098, [email protected] | | | |
| |