Plan Review Notes
Plan Review Notes For Project Z20080008
Project Number Z20080008
Review Stop STORM
Sequence Number 2
Notes
Date Text
2021-04-06 11:41:46THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 3/31/2021 SUBMITTAL. THEY CAN BE ADDRESSED DURING
 ENGINEERING PERMIT SUBMITTAL.
  
 1. SHOW ON THE DEMOLITION PLAN, SHEET C-03, THE
 EXISTING DRAINAGE PIPE CONNECTIONS FOR THE TWO CATCH
 BASINS IN THE NORTHEAST AREA OF THE SITE.
  
 2. THE PGD PLAN (SHEET C-04) CALLS OUT 8' X 10'
 EXFILTRATION TRENCH BUT THE EXFILTRATION TRENCH DETAIL
 ON SHEET C-06 SHOWS 10' X 6.5' TRENCH DIMENSIONS.
  
 3. THE EXFILTRATION TRENCH DETAIL SHOWS A WEIR
 ELEVATION OF 15.70 FT NAVD.
 A. WHERE IS THIS WEIR LOCATED?
 B. LOWEST FINISHED GRADE IS 16.10. SUGGEST USING
 CRUSHED CONCRETE BASE INSTTEAD OF LIMEROCK BASE TO
 CONTEND WITH POTENTIAL SATURATED BASE CONDITIONS.
 C. THE PROPOSED FINISHED GRADE OF THE LAWN OVER THE
 RAINTANKS IS SHOWN TO BE 16.50' NAVD. SHOULD THE
 FINISHED GRADE BE A MINIMUM OF 1 FOOT ABOVE THE WEIR
 ELEVATION?
  
 4. ADD VERTICAL DATUM REFERENCE AND CONVERSION EQUATION
 TO NGVD1929 ON EVERY SHEET WITH ELEVATION INFORMATION.
  
 5. SHOW MINIMUM HORIZONTAL CLEARANCE BETWEEN S.S.M.H.
 #4 AND THE 8" WATER MAIN TO THE NORTH AND NORTHWEST OF
 THE STRUCTURE.
  
 6. CHECK WITH LAURA LE, PUBLIC UTILITIES ENGINEERING,
 WHETHER TO INCLUDE IN THE DESIGN OF THE PROPOSED
 SANITARY SYSTEM ON CLEARWATER DRIVE THE 0.1' DROP
 ACROSS THE MANHOLES AS INDICATED ON THE SEWER MANHOLE
 DETAIL.
  
 7. IF THE TRENCH CUT FOR THE PROPOSED 12" WATER MAIN IS
 WITHIN THE NORTHBOUND LANE OF CLEARWATER DRIVE, THE
 FULL WIDTH OF THE NORTHBOUND LAND WILL NEED TO BE
 MILLED AND RE-SURFACED.
  
 8. AVOID HAVING VALVE COVERS FALL WITHIN THE CURB AND
 GUTTER.
  
 9. THE EXISTING WATER MAIN WILL NEED TO BE PROPERLY
 RESTRAINED DUE TO THE PIPE DEFLECTIONS AND VALVES.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120 (O)
 561-351-0510 (M)
  
  