| Date |
Text |
| 2020-10-28 15:17:35 | COMMENTS PER RICK ROSSANO: |
| | 1. ADD ADDRESS TO COVER SHEET. |
| | 2. PROVIDE SWPPP FOR ENGINEERING SUBMITTAL SPECIFYING |
| | STORM INLET PROTECTION ONSITE AND ALONG ENTIRE FRONTAGE |
| | OF PROJECT. |
| | |
| | SHEET C-08: |
| | 1. ADD NOTE TO REMOVE 8 IN. SANITARY TO BE ABANDONED. |
| | 2. ADD NAVD/NGVD CONVERSION NOTE. |
| | |
| | SHEET C-10: |
| | 1. UPDATE SANITARY SEWER STANDARD DETAILS TO MOST |
| | CURRENT VERSIONS; EMAIL [email protected] FOR PDF |
| | VERSIONS OR [email protected] FOR CAD VERSIONS. |
| | 2. FOR MANHOLES IN RIGHT OF WAY, PROVIDE 5 FT. MIN. |
| | INTERNAL DIAMETER. |
| | |
| | COMMENTS PER MARK HURLEY: |
| | |
| | -NEED UPDATE DEMO PLAN C-03 LABELS TO REFLECT THAT |
| | EXISTING WATER SERVICES AND BACKFLOW ASSEMBLIES FOR |
| | PHASE ONE ARE NOT BEING RELOCATED OR CHANGED UNTIL |
| | DOWNSTREAM OF THE BACKFLOW ASSEMBLIES, AS INDICATED IN |
| | PRIOR COMMENT RESPONSES. |
| | |
| | -ON UTILITY PLAN C-08, RELOCATE GATE VALVES FOR NEW |
| | WATER SERVICES OUT OF THE SIDEWALK. |
| | |
| | -PROPOSED DOMESTIC 6 INCH METER IS STILL TOO FAR FROM |
| | THE PROPERTY LINE. POSSIBLE SOLUTION MAY BE TO RELOCATE |
| | FIRE AND IRRIGATION WATER SERVICES SOUTH OF THE GUY |
| | ANCHOR EASEMENT, AND RELOCATE THE DOMESTIC METER EAST |
| | (STILL NORTH OF THE GUY ANCHOR EASEMENT). |
| | |
| | -FOR FORMAL ENGINEERING SUBMITTAL, ADD LABELS TO THE |
| | CITY WATER SERVICE PIPING SHOWING PIPE SIZE AND |
| | MATERIAL TYPE USED. ALSO ADD LABELS ON THE REROUTED |
| | PRIVATE PIPING FOR THE EXISTING WATER SERVICES THAT |
| | SHOW PIPE MATERIAL FOR THE FIRE AND IRRIGATION LINES. |
| | |
| | -FOR FORMAL ENGINEERING SUBMITTAL, UPDATE LABELS FOR |
| | IRRIGATION METER AND BACKFLOW ASSEMBLY TO REFERENCE |
| | WS-1 AND WS-6 RESPECTIVELY. |
| | |
| | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR |
| | CONCERNS, THANKS. |
| | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES |
| | DEPARTMENT, 561-494-1098, [email protected] |
| | |
| |